Plan Review Notes
Plan Review Notes For Permit 08070071
Permit Number 08070071
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-23 15:18:541. THE REQUIREMENTS OF NFPA 303, THE STANDARD FOR
 MARINA'S AND BOATYARDS SHALL BE COMPLIED WITH.
  
 2.THE FIRE DEPARTMENT CONNECTION (FDC) APPEARS TO FACE
 THE DOCK. THIS CONNECTION SHALL FACE THE STREET AND BE
 WITHIN ONE HUNDRED FIFTY (150) FEET OF A HYDRANT.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 STANDPIPE SYSTEM.
  
 4. THE BACKFLOW PREVENTION DEVICE FOR THE FIRE LINE AND
 STANDPIPE SYSTEM SHALL BE CHAINED AND LOCKED TO PREVENT
 CLOSURE.
  
 5. ALL STAIRS SHALL BE SLIP RESISTANT.
  
 6. ALL ELECTRICAL INSTALLATIONS TO COMPLY WITH NFPA 70,
 THE NATIONAL ELECTRICAL CODE.
  
 7. THE ENTIRE FIRE LINE AND FIRE DEPARTMENT CONNECTION
 SHALL BE PRESSSURE TESTED FOR A MINIMUM OF AT LEAST TWO
 HOURS ATE 200 PSIG PRIOR TO RECEIVING APPROVAL.
  
 8. A SMOKING POLICY NEEDS TO BE DEVELOPED.
  
 9. A METHOD TO REPORT EMERGENCIES SHALL BE PROVIDED SO
 THAT EMERGENCY SERVICE PERSONNEL CAN BE CONTACTED.
  
 10. THE PORTABLE FIRE EXTINGUISHERS THAT ARE TO BE
 PLACED INTO THE STORAGE FIXTURES SHALL BE PROPERLY
 SERVICE TAGGED.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION