2008-07-09 11:15:29GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. NOTE: THERE IS A GAS PERMIT NUMBER 07110574, BY
 CONTRACTOR "FLORIDA PUBLIC UTILITIES CO.", THAT HAS
 BEEN APPLIED FOR AND APPROVED ON 4/04/08 THAT WAS
 SUBMITTED WITH GEN/RES PERMIT #08030561, WHICH IS NOW
 VOID. THAT GAS PERMIT APPLICATION AND PLANS NEEDS TO BE
 RESUBMITTED WITH THE NEW GEN/RES PERMIT APPLICATION IN
 ORDER TO RECEIVE THE GENERATOR PERMIT OR VOID THAT
 PERMIT AND APPLY FOR A NEW GAS PERMIT WITH NEW PLANS.
 PER FBC- FUEL GAS CODE SECTION 401.1 SCOPE.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 2. MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES. PER FBC-FUEL GAS CODE SECTION 401.1 SCOPE.
  
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731