Plan Review Notes
Plan Review Notes For Permit 08070031
Permit Number 08070031
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-08 12:40:58 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING IS REQUIRED TO BE SUBMITTED FOR REVIEW.
  
 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED
 LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM
 PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE
 THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST
 CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE
 RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR
 DETAILS REGARDING SETBACKS.
  
 2} MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718