2008-07-01 16:21:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE PRODUCT APPROVAL SUBMITTED FOR THE BUILDING
 PERMIT (AND REVIEWED BY DESIGNER OF RECORD) WAS
 NOA05-0919.06 WHICH HAS A DP OF -76.8 FIELD, -84.3
 PERIMETER/CORNER.THE DESIGN PRESSURE FOR THE JOB,
 "CLADDING -83.1 ALL ZONES" REQUIRES THAT ZONE 2&3
 FASTENING BE USED ON THE ENTIRE JOB.THE PRODUCT
 APPROVAL SUBMITTED HAS A DESIGN PRESSURE LIMITATION OF
 -59.4 AND -97.5.
  
 TO USE THE NEW PRODUCT, ADVANTAGE-LOK II RATHER THAN
 ADVANTAGE LOK STANDING SEAM 26 GAGE, PLEASE SUBMIT AS A
 REVISION TO THE BUILDING PERMIT.HAVE THE PRODUCT
 APPROVAL REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL.
  
 THE PERMIT WILL BE ISSUED WITH A PROVISO THAT ZONE 3
 FASTENING BE USED ON THE ENTIRE ROOF, ZONES 1, 2, AND
 3, UNLESS THE BUILDING PERMIT IS REVISED TO REDUCE THE
 DESIGN PRESSURE REQUIREMENT FOR THE ROOF.TO CLARIFY,
 PLEASE MARK ON PAGE 3 OF THE PRODUCT APPROVAL WHICH
 FASTENING YOU PROPOSE TO USE FOR EACH ZONE.
  