Plan Review Notes For Permit 08060901
Permit Number 08060901
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-08 15:58:42 
  
  
  
 GENERATOR PERMITS MUST BE APPLIED FOR SEPARATELY AND
 THE FOLLOWING IS REQUIRED
  
 ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO
 EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS,
 SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF
 ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER
 108.3 WPB AMENDMENTS. INDICATE FUEL TYPE AND KW RATING
 ON THE APPLICATION.
  
 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED
 LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM
 PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE
 THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST
 CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE
 RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR
 DETAILS REGARDING SETBACKS.
  
 2} A GAS PERMIT MUST BE APPLIED FOR NATURAL GAS OR LP
 FUELED GENERATORS. SUBMIT INFORMATION COMPLIANT WITH
 THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENT.
  
 3} A FUEL PERMIT IS REQUIRED FOR GASOLINE OR DIESEL.
  
 4} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE
 THE FOLLOWING:
  
 A) GENERATOR AND TRANSFER SWITCH MANUFACTURER
 SPECIFICATIONS.
 1) THE TRANSFER SWITCH MUST BE SIZED FOR THE SELECTED
 LOADS.
  
 B) RISER DIAGRAM SHOWING LOCATIONS OF ALL EQUIPMENT
 ELECTRICALLY.
  
 C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE
 EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE
 STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE
 RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF
 LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO
 110.9 FOR AIC RATING.
  
 D) MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES.
  
 E) IDENTIFY LOADS TO BE SERVED, PROVIDE A PANEL
 SCHEDULE FOR GENERATOR PANEL.
  
 F) LOADS MUST NOT EXCEED GENERATOR OUTPUT. SUBMIT A
 LOAD CALCULATION FOR THE LOADS TO BE SERVED IF AN
 AUTOMATIC TRANSFER SWITCH IS BEING INSTALLED.
  
 G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS
 INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL
 BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND
 TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING.
  
 SEE ARTICLES 445 AND 702 FOR ADDITIONAL INFORMATION.
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718