2008-07-08 15:58:42 | |
| |
| |
| |
| GENERATOR PERMITS MUST BE APPLIED FOR SEPARATELY AND |
| THE FOLLOWING IS REQUIRED |
| |
| ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO |
| EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS, |
| SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF |
| ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER |
| 108.3 WPB AMENDMENTS. INDICATE FUEL TYPE AND KW RATING |
| ON THE APPLICATION. |
| |
| 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED |
| LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM |
| PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY |
| EASEMENTS INVOLVED. THE GENERATOR MAY NOT INTRUDE MORE |
| THAN 4 (FOUR) FEET INTO A SETBACK, AND MAY NOT EXHAUST |
| CLOSER THAN 5 (FIVE) FEET TO A DIRECT OPENING IN THE |
| RESIDENCE. CONTACT THE WPB ZONING DEPARTMENT FOR |
| DETAILS REGARDING SETBACKS. |
| |
| 2} A GAS PERMIT MUST BE APPLIED FOR NATURAL GAS OR LP |
| FUELED GENERATORS. SUBMIT INFORMATION COMPLIANT WITH |
| THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENT. |
| |
| 3} A FUEL PERMIT IS REQUIRED FOR GASOLINE OR DIESEL. |
| |
| 4} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE |
| THE FOLLOWING: |
| |
| A) GENERATOR AND TRANSFER SWITCH MANUFACTURER |
| SPECIFICATIONS. |
| 1) THE TRANSFER SWITCH MUST BE SIZED FOR THE SELECTED |
| LOADS. |
| |
| B) RISER DIAGRAM SHOWING LOCATIONS OF ALL EQUIPMENT |
| ELECTRICALLY. |
| |
| C) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE |
| EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE |
| STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE |
| RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF |
| LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO |
| 110.9 FOR AIC RATING. |
| |
| D) MANUFACTURER SETBACK RECOMMENDATIONS FROM |
| STRUCTURES. |
| |
| E) IDENTIFY LOADS TO BE SERVED, PROVIDE A PANEL |
| SCHEDULE FOR GENERATOR PANEL. |
| |
| F) LOADS MUST NOT EXCEED GENERATOR OUTPUT. SUBMIT A |
| LOAD CALCULATION FOR THE LOADS TO BE SERVED IF AN |
| AUTOMATIC TRANSFER SWITCH IS BEING INSTALLED. |
| |
| G) THE INSTALLATION OF THE SLAB, PAD OR BASE IS |
| INCIDENTAL TO THE ELECTRICAL CONTRACTOR?S SCOPE. WILL |
| BE REQUIRED TO BE INSPECTED. PROVIDE ENGINEERING AND |
| TIE DOWN SPECIFICATIONS FOR 140 MPH WIND LOADING. |
| |
| SEE ARTICLES 445 AND 702 FOR ADDITIONAL INFORMATION. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |