Plan Review Notes For Permit 08060698 |
Permit Number |
08060698 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-09-29 13:37:38 | *****DENIED***** | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW | | STILL NEED TO BE ADDRESSED: | | | | 1. MINIMUM 2A-10BC RATED FIRE EXTINGUISHER(S) SHALL BE | | MOUNTED. SHOW THE LOCATION OF FIRE EXTINGUISHER(S) ON | | THE APPROPIATE PLAN SHEET. | | | | 2. RAMP TO COMPLY WITH NFPA 101, SEC 7.2.5. YOUR | | RESPONSE LETTER INDICATES THAT THE WIDTH OF THE RAMP | | HAS BEEN INCREASED TO 3' - 8" WITH NO OBSTRUCTIONS IN | | THAT WIDTH, HOWEVER PLAN SHEET SHOWS 3' - 6" ITS WIDTH | | | | 3. ADDRESS SHALL BE A MINUMUM OF 6" IN HEIGHT, 1" WIDTH | | AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL | | BUILDINGS. COULD NOT LOTATE THIS NOTE ON SHEET SP-1 AS | | PER YOUR RESPONSE LETTER. DISPLAY/SHOW THE NUMERICAL | | ADDRESS ON THE APPROPIATE EXTERIOR ELEVATION OF THE | | STRUCTURE WHICH FRONTS PONCE DE LEON AVENUE | | | | 4. LOCKS TO COMPLY WITH NFPA 101, SEC 7.2.1.5. COULD | | NOT LOTATE THIS NOTE ON SHEET A-1 AS PER YOUR RESPONSE | | LETTER | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | EACH ITEM WAS ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|