Plan Review Notes
Plan Review Notes For Permit 08060698
Permit Number 08060698
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-09-29 13:37:38*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
 1. MINIMUM 2A-10BC RATED FIRE EXTINGUISHER(S) SHALL BE
 MOUNTED. SHOW THE LOCATION OF FIRE EXTINGUISHER(S) ON
 THE APPROPIATE PLAN SHEET.
  
 2. RAMP TO COMPLY WITH NFPA 101, SEC 7.2.5. YOUR
 RESPONSE LETTER INDICATES THAT THE WIDTH OF THE RAMP
 HAS BEEN INCREASED TO 3' - 8" WITH NO OBSTRUCTIONS IN
 THAT WIDTH, HOWEVER PLAN SHEET SHOWS 3' - 6" ITS WIDTH
  
 3. ADDRESS SHALL BE A MINUMUM OF 6" IN HEIGHT, 1" WIDTH
 AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL
 BUILDINGS. COULD NOT LOTATE THIS NOTE ON SHEET SP-1 AS
 PER YOUR RESPONSE LETTER. DISPLAY/SHOW THE NUMERICAL
 ADDRESS ON THE APPROPIATE EXTERIOR ELEVATION OF THE
 STRUCTURE WHICH FRONTS PONCE DE LEON AVENUE
  
 4. LOCKS TO COMPLY WITH NFPA 101, SEC 7.2.1.5. COULD
 NOT LOTATE THIS NOTE ON SHEET A-1 AS PER YOUR RESPONSE
 LETTER
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW