2008-09-23 10:21:13 | BUILDING PLAN REVIEW |
| PERMIT: 08060698 |
| ADD: 2048 PONCE DE LEON |
| CONT: JB KERN CONST. |
| TEL: (561)762-4849 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 9-23-08 |
| REVIEW: 2ND |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| **NOTED** THE PLANS DO NOT MEET THE REQUIREMENTS. RAMPS |
| AND LANDINGS WITH DROP-OFFS SHALL HAVE A MINIMUM CURB |
| OF 2 INCHES. 11-4.8.7 AND FIG 17. THE CLEAR WIDTH SHALL |
| BE 44". |
| 2) 11-4.8.3 THE MINIMUM CLEAR WIDTH OF A RAMP SHALL BE |
| 36 INCHES. HOWEVER, RAMPS THAT ARE PART OF A REQUIRED |
| MEANS OF EGRESS SHALL BE NOT LESS THAN 44 INCHES WIDE. |
| |
| **NOTE; 1;48 SLOPES MORE THAT 1;50. THEREFORE, THE 1;48 |
| DO NOT MEET THE REQUIREMENTS. |
| 3) 11-4.8.6 THE CROSS SLOPE OF RAMP SURFACES SHALL BE |
| NO GREATER THAN 1:50. RAMP SURFACES SHALL COMPLY WITH |
| SECTION. 11-4.5. |
| |
| 4) 11-4.17.3 THE SIZE AND ARRANGEMENT OF THE STANDARD |
| TOILET STALL SHALL COMPLY WITH FIGURE 30(A). SEE DETAIL |
| (C) ON SHEET A-2. |
| |
| WHAT IS THE SLOPE OF THE RAMP? STATE THE INFORMATION ON |
| THE PLANS. SEE 11-4.8. |
| 5) INDICATE THE DIMENSIONS OF THE SLOPE AND LANDING OF |
| THE RAMP ON THE SHEET A-2 DETAIL D-3. |
| |
| NOTE: WHEN RESUBMITTING, PLEASE MAKE SURE TWO SETS OF |
| PLANS ARE BOUND TOGETHER. LOOSE PAGES ARE NOT |
| ACCEPTABLE. THANKS. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |