2008-07-18 10:28:02PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET SP-1 PLUMBING FIXTURE CALCULATIONS: THE
 INDICATED PLUMBING CALCULATIONS ON THIS SHEET ARE
 WRONG. PER FBC- PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES FOR AN OCCUPANCY BROUP B-
 BUSSINESS ARE AS FOLLOWS.
  
 *WATER CLOSETS MALE/FEMALE= 1 PER 25 FOR THE FIRST 50
 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50.
  
 *LAVATORIES MALE/FEMALE= 1 PER 40 FOR THE FIRST 50 AND
 1 PER 80 FOR THE REMAINDER EXCEEDING 50.
  
 *DRINKING FOUNTAIN= 1 PER 100.
  
 PLEASE CORRECT THESE CALCULATIONS ON THE RESUBMITTAL.
  
 2. SHEET A-2 DETAIL B, H.C. BATHROOM INT. ELEVATION:
 THE GRAB BAR BEHIND THE WATER CLOSET SHALL BE 36 INCHES
 MINIMUM. PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE SECTION 11-4.16.4 GRAB BARS.
  
 3. SHEET A-2 DETAIL D-2, DRINKING FOUNTAIN DETAIL. PER
 FBC- CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTION
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3 PLUMBING
 (4)(6)(13): PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND
 SIZES WITH CLEANOUT LOCATIONS FOR THE PROPOSED NEW H.C.
 BATHROOM AND DRINKING FOUNTAIN.
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
 NOTE: CLEARLY INDICATE ON THE PLANS WHAT IS EXISTING
 AND WHAT IS NEW ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  