Plan Review Notes
Plan Review Notes For Permit 08060698
Permit Number 08060698
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-22 10:25:36 
 BUILDING PLAN REVIEW
 PERMIT: 08060698
 ADD: 2048 PONCE DE LEON
 CONT: JB KERN CONST.
 TEL: (561)762-4849
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 11-4.8.3 THE MINIMUM CLEAR WIDTH OF A RAMP SHALL BE
 36 INCHES. HOWEVER, RAMPS THAT ARE PART OF A REQUIRED
 MEANS OF EGRESS SHALL BE NOT LESS THAN 44 INCHES WIDE.
  
 3) 11-4.8.6 THE CROSS SLOPE OF RAMP SURFACES SHALL BE
 NO GREATER THAN 1:50. RAMP SURFACES SHALL COMPLY WITH
 SECTION. 11-4.5.
  
 4) 11-4.17.3 THE SIZE AND ARRANGEMENT OF THE STANDARD
 TOILET STALL SHALL COMPLY WITH FIGURE 30(A). SEE DETAIL
 (C) ON SHEET A-2.
  
 5) INDICATE THE DIMENSIONS OF THE SLOPE AND LANDING OF
 THE RAMP ON THE SHEET A-2 DETAIL D-3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]