Plan Review Notes For Permit 08060678 |
Permit Number |
08060678 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-01 09:57:20 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} 13-101.1 COMMERCIAL BUILDINGS. | | 13-101.1.1 NEW CONSTRUCTION. | | SUBCHAPTER 13-4, COMMERCIAL BUILDING COMPLIANCE | | METHODS. COMMERCIAL BUILDINGS OF ANY SIZE AND | | MULTIPLE-FAMILY RESIDENTIAL BUILDINGS GREATER THAN | | THREE STORIES SHALL COMPLY WITH SUBCHAPTER 13-4 OF THE | | CODE. | | SEE13-415.2.C PERFORMANCE CALCULATION PROCEDURES | | SPECIFIC TO METHOD C.*.08 WATTS PER SQUARE FOOT. SUBMIT | | A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE PLAN TO | | CORRELATE WITH THE ONES IN THE CALCULATIONS. | | | | 2} THE PLANS SUBMITTED ON 6/19/08 FOR PHASE 1 WITH THE | | ENGINEERS SEAL DATED 5/23/08 AND THE PLANS SUBMITTED | | FOR PHASE 2, ENGINEERS SEAL DATED 5/19/08 HAVE | | DIFFERENT SIGNATURES. THE PLANS WILL BE RETAINED PER | | FBPE INSTRUCTIONS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|