Plan Review Notes
Plan Review Notes For Permit 08060678
Permit Number 08060678
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-01 09:57:20 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-101.1 COMMERCIAL BUILDINGS.
 13-101.1.1 NEW CONSTRUCTION.
 SUBCHAPTER 13-4, COMMERCIAL BUILDING COMPLIANCE
 METHODS. COMMERCIAL BUILDINGS OF ANY SIZE AND
 MULTIPLE-FAMILY RESIDENTIAL BUILDINGS GREATER THAN
 THREE STORIES SHALL COMPLY WITH SUBCHAPTER 13-4 OF THE
 CODE.
 SEE13-415.2.C PERFORMANCE CALCULATION PROCEDURES
 SPECIFIC TO METHOD C.*.08 WATTS PER SQUARE FOOT. SUBMIT
 A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE PLAN TO
 CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 2} THE PLANS SUBMITTED ON 6/19/08 FOR PHASE 1 WITH THE
 ENGINEERS SEAL DATED 5/23/08 AND THE PLANS SUBMITTED
 FOR PHASE 2, ENGINEERS SEAL DATED 5/19/08 HAVE
 DIFFERENT SIGNATURES. THE PLANS WILL BE RETAINED PER
 FBPE INSTRUCTIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718