2008-08-20 17:10:00BUILDING PLAN REVIEW
 PERMIT: 08060669
 ADD: 400 N. FLAGLER DR. #605
 CONT: HAWKES & DANIEL CONSTRUCTION
 TEL: (561)315-2525
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 **NO COMMENT NOT ADDRESSED**
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 NO INFORMATION WAS SUBMITTED FOR THE SOFFITS. ELEVATION
 DETAILS REQUIRED. WHAT IS THE NEW OPENING DIMENSIONS?
 5)PROVIDE ELEVATION DETAILED ARCHITECTURAL DRAWINGS
 TO CLEARLY SHOW THE WORK. WILL BE SOFFIT BE INSTALLED
 THROUGHOUT THE SPACE?SUBMIT THE FRAMING DETAILS FOR
 THE NEW WALLS AND SOFFITS SHOWING THE STRUCTURAL
 ATTACHMENTS AND ALL MATERIALS.
  
 6)OK
 7)OK
 8)OK.
 9)OK
  
 **NO COMMENT NOT ADDRESSED**
 10) 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492. PROVIDE INFORMATION MEETING THIS REQUIREMENT OR
 INDICATE ON THE PLANS THE TYPE OF CORK WHICH WILL BE
 USED UNDER THE TILES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726