| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| SECTION 611 (EXISTING BIDING CODE). |
| ENERGY CONSERVATION |
| 611.1MINIMUM REQUIREMENTS. |
| ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH |
| THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| 1}PER CHAPTER 13 FBC, SUBCHAPTER 13-400.0.C.4, |
| PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER |
| 13-415.2. SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES |
| ON THE PLAN TO CORRELATE WITH THE ONES IN THE |
| CALCULATIONS.THIS PRESCRIPTIVE METHOD CAN BE SHOWN ON |
| THE ELECTRICAL PLAN |
| |
| 2} 13-415.1.ABC.1.2 SPACE CONTROL. |
| EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A |
| CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY |
| TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS |
| LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL, |
| IN THE FOLLOWING: 1. CLASSROOMS (NOT INCLUDING SHOP |
| CLASSROOMS, LABORATORY CLASSROOMS, AND PRESCHOOL |
| THROUGH 12TH GRADE CLASSROOMS). 2. CONFERENCE/MEETING |
| ROOMS. |
| 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| INDICATE COMPLIANCE WITH THESE SECTIONS ON THE PLAN. |
| |
| 3} THERE ARE FOUR RECEPTACLES LOCATED OFF THE WALL IN |
| THE CONFERENCE ROOM (1801) SHEET E-1THAT ARE NOT MARKED |
| AS TO A CEILING INSTALLATION OR FLOOR INSTALLATION, |
| PLEASE CLARIFY. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |