2008-07-01 14:50:22 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET 3.1 PARTIAL FLOOR PLAN INDICATES THE REMOVAL |
| OF A BATHROOM AND CHANGING THE TOILET ROOM TO AN |
| EQUIPMENT ROOM, HOWEVER THERE IS NO INDICATION THAT THE |
| EXISTING BUILDING IS COMPLIANT PER THE FOLLOWING FBC- |
| PLUMBING TABLE 403.1 MINIMUM NUMBER OF REQUIRED |
| PLUMBING FIXTURES FOR BUSSINESS (B). PLEASE CLEARLY |
| INDICATE THE OCCUPANCY LOAD ON SHEET 1.1 CODE SUMMARY |
| AND COMPLY WITH THE FOLLOWING. |
| |
| A}WATER CLOSETS MALE/FEMALE = 1 PER 25 FOR THE FIRST |
| 50 AND 1 PER 50 FOR THE REMAINDER EXCEEDING 50. |
| |
| B} LAVATORIES MALE/FEMALE = 1 PER 40 FOR THE FIRST 50 |
| AND 1 PER 80 FOR THE REMAINDER EXCEEDING 50. |
| |
| C} DRINKING FOUNTAINS = 1 PER 100. |
| |
| 2. SHEET 3.1 DEMO OF TOILET ROOM, PLEASE ADD THE |
| FOLLOWING TO GERERAL PROJECT NOTES: PER FBC-2004 |
| PLUMBING, SECTION 704.5 DEAD ENDS: IN THE REMOVAL OF |
| ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND AN |
| INSPECTION IS REQUIRED OF THE PLUMBING DEMO WORK PRIOR |
| TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR |
| POURED CONCRETE SLABS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |