2008-06-24 15:01:41 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} AN ELEVATION PLAN OF ROOM 103 SHEET ME1IS REQUIRED | | PER 106.1.1 FBC TO DETERMINE COMPLIANCE WITH 110.13 AND | | 110.26. | | | | SHEET ME2 | | | | 2} THE SECOND SERVICE WILL BE ALLOWED UNDER EXCEPTION | | 230.2(D)BUT IT MUST BE IDENTIFIED PER 230.2(E) AND | | GROUPED PER 230.72.NOTE COMPLIANCE WITH THESE ARTICLES | | ON THE PLAN. | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | 250.104(D)(3). BOND BOTH GEC'S FROM SEPARATELY DERIVED | | SYSTEMS TOGETHER. INDICATE SAME ON THE PLANS. | | | | 4} THE PRIMARY OCP FOR THE TRANSFORMER MUST COMPLY WITH | | ARTICLE 450.4, WHICH IS 80 AMPS @ 125%.THE FIRST MEANS | | OF DISCONNECT IS SHOWN AS 100 AMPS, THE TRANSFORMER | | DISCONNECT IS RATED AT THE SAME. INDICATE AN OCP OF 80 | | AMPS FROM THE TRANSFORMER DISCONNECT. | | | | 5} THE FEEDER FROM THE FIRST MEANS OF DISCONNECT TO THE | | TRANSFORMER MUST CONTAIN AN EQUIPMENT GROUND PER | | 250.122, AND SIZED PER SAME. INCLUDE THIS ON THE PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | FAX/:561/805-6676 |
|