Plan Review Notes
Plan Review Notes For Permit 08060628
Permit Number 08060628
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-24 15:01:41 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AN ELEVATION PLAN OF ROOM 103 SHEET ME1IS REQUIRED
 PER 106.1.1 FBC TO DETERMINE COMPLIANCE WITH 110.13 AND
 110.26.
  
 SHEET ME2
  
 2} THE SECOND SERVICE WILL BE ALLOWED UNDER EXCEPTION
 230.2(D)BUT IT MUST BE IDENTIFIED PER 230.2(E) AND
 GROUPED PER 230.72.NOTE COMPLIANCE WITH THESE ARTICLES
 ON THE PLAN.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.104(D)(3). BOND BOTH GEC'S FROM SEPARATELY DERIVED
 SYSTEMS TOGETHER. INDICATE SAME ON THE PLANS.
  
 4} THE PRIMARY OCP FOR THE TRANSFORMER MUST COMPLY WITH
 ARTICLE 450.4, WHICH IS 80 AMPS @ 125%.THE FIRST MEANS
 OF DISCONNECT IS SHOWN AS 100 AMPS, THE TRANSFORMER
 DISCONNECT IS RATED AT THE SAME. INDICATE AN OCP OF 80
 AMPS FROM THE TRANSFORMER DISCONNECT.
  
 5} THE FEEDER FROM THE FIRST MEANS OF DISCONNECT TO THE
 TRANSFORMER MUST CONTAIN AN EQUIPMENT GROUND PER
 250.122, AND SIZED PER SAME. INCLUDE THIS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676