2008-07-09 11:29:47 | BUILDING PLAN REVIEW |
| PERMIT: 08060628 |
| ADD: 1201 N. OLIVE AVE |
| CONT: ANDERSON-MOORE CONSTRUCTION |
| TEL: (561)753-7400 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 7-9-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT |
| ARE REGULATED BY DCA |
| RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVAL |
| FOR THE NEW EXTERIOR DOOR. |
| |
| 5) FOR CLARITY PROVIDE AN EXISTING FLOOR PLAN SHOWING |
| ALL WALLS, DOORS, WINDOWS AND ANY OTHER SYSTEMS LOCATED |
| IN THE AREA WHICH WILL BE DEMOED: THEN, THE PROPOSED |
| PLAN NEEDS TO CLEARLY SHOW ALL NEW SYSTEMS AND DOORS |
| WHICH WILL BE INSTALLED AND THE HOW THE ROOM WILL BE |
| LAID OUT WHEN FINISHED. SHEET 3.1 HAS SOME OF THIS |
| INFORMATION HOWEVER, I AM NOT SURE IF THE NEW DOORS |
| MENTIONED (NEW LED FILLED SLIDING AND SWING DOOR / NEW |
| 3'-0 X 7'-0 METAL DOOR ARE INSTALLED AT PRESENT AND |
| WILL BE REPLACED WITH THE DOOR BUT THE FRAME IS |
| EXISTING. IF THESE ARE COMPLETE NEW DOORS THEY SHALL |
| MEET THE REQUIREMENTS OF FBC 1714.5. UNLESS OTHER WISE |
| TESTED, BUCKS SHALL EXTEND BEYOND THE INTERIOR FACE OF |
| THE WINDOW OR DOOR FRAME SUCH THAT FULL SUPPORT OF THE |
| FRAME IN PROVIDED.106.1.2* ADDITIONAL INFORMATION IS |
| REQUIRED TO CLEARLY SHOW THE INTENT OF THE REMODEL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THE CODE. 106.1.1. WHAT IS THE SIZE OF |
| THE CONCRETE PADS FOR THE NEW CONDENSING UNITS? SHOW |
| THE DETAIL INFORMATION FOR THE SLABS ON THE DRAWINGS. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |