Plan Review Notes For Permit 08060620
Permit Number 08060620
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-06-24 19:02:161. NEW FIRE MAIN PLANNED TO BE INSTALLED SHALL BE
 PROPERLY SUPPORTED AND RETRAINED.
  
 2. ALL PORTIONS OF THE NEW FIRE MAIN SHALL BE PRESSURE
 TESTED AT 200 PSIG FOR A MINIMUM OF AT LEAST TWO
 HOURS.
  
 3. THE NEW FIRE MAIN SHALL BE INSTALLED IN ACCORDANCE
 WITH NFPA 24, THE STANDARD FOR FIRE SERVICE MAINS AND
 THEIR APPURTENANCES.
  
 4. THE NEW MAIN SHALL BE INSTALLED IN AN APPROVED AND
 PROFESSIONAL MANNER.
  
 5. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
 6. ENTIRE INSTALLATION MUST BE INSPECTED, TESTED, AND
 APPROVED BY THE BUREAU OF FIRE PREVENTION PRIOR TO THIS
 LINE BEING PLACED INTO SERVICE.
  
 7. AFTER APPROVAL, THIS INSTALLATION MUST BE PERFORMED
 IN A TIMELY MANNER AS THE BUILDING IS AND HAS BEEN
 CURRENTLY ON FIRE WATCH DUE TO A PORTION OF THE
 UNDERGROUND FIRE MAIN LEAKING.
  
 8. AREAS THAT WERE EXCAVATED OR EXPOSED IN AN ATTEMPT
 TO LOCATE THE LEAK SHALL BE REPAIRED TO AS NEAR AS
 ORIGINAL CONDITION AS POSSIBLE TO PREVENT POSSIBLE
 INJURIES.
  
 9. VERIFICATION THAT ANY SECTIONAL OR ISOLATION VALVES
 ARE OPENED AND REMAIN IN THAT POSITION AFTER
 INSTALLATION.
  
 10. METHODS OR DEVICES SHALL BE INSTALLED TO ALLOW FOR
 INSPECTION OF THIS PIPING ARRANGEMENT AFTER
 INSTALLATION.
  
  