Plan Review Notes
Plan Review Notes For Permit 08060582
Permit Number 08060582
Review Stop Z
Sequence Number 1
Notes
Date Text
2008-07-14 13:35:14***FAILED***
  
 1) THE DRIVE AISLE ADJACENT TO THE GENERATOR WILL NEED
 TO BECOME ONE-WAY, AS IT WILL ONLY BE 15 FEET IN WIDTH.
 I SUGGEST THAT A "DO NOT ENTER" SIGN BE INSTALLED IN
 THE LANDSCAPE ISLAND TO PREVENT PEOPLE FROM DRIVING
 SOUTH THROUGH THE AISLE (SEE ATTACHED SKETCH FOR
 LOCATION OF SIGN).
  
 2) AS NOTED PREVIOUSLY, ALL MECHANICAL EQUIPMENT WILL
 NEED TO BE SCREENED PURSUANT TO SECTION 94-444(B) OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS):
  
 A) THE PROPOSED PVC FENCE SHALL COMPLETELY ENCLOSE THE
 GENERATOR.
 B) THE FENCE SHALL BE LANDSCAPE WITH SHRUBS/HEDGES
 PLANTED AT 2 FOOT INTERVALS.
 C) THE SHRUBS/HEDGES SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT BY MEANS OF CURBING.
 D) THE SWITCHGEAR AND TRANSFORMER SHALL ALSO BE
 PROPERLY SCREENED.
  
 QUESTIONS/COMMENTS CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
2008-07-09 17:34:05PLANNING AND ZONING:
  
 CURRENTLY PENDING MINOR AMENDMENT REVIEW FROM THE
 PLANNING AND ZONING DEPT.
  
 ANY QUESTIONS, PLEASE CONTACT JOHN ROACH AT 822-1448.