Plan Review Notes For Permit 08060582 |
Permit Number |
08060582 |
|
Review Stop |
FUEL |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-17 14:05:36 | *** PROVISO *** | | 1) FUEL STORAGE TANK MUST BE A MINIMUM OF 5 FEET FROM | | THE BUILDING, PER NFPA 30 4.3.2.1.1. | | | | 2) THE GENERATOR MUST BE A MINIMUM OF 5 FEET FROM ANY | | BUILDING OPENINGS, PER NFPA 37 4.1.4. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 |
|