2008-07-17 14:05:36*** PROVISO ***
 1) FUEL STORAGE TANK MUST BE A MINIMUM OF 5 FEET FROM
 THE BUILDING, PER NFPA 30 4.3.2.1.1.
  
 2) THE GENERATOR MUST BE A MINIMUM OF 5 FEET FROM ANY
 BUILDING OPENINGS, PER NFPA 37 4.1.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729