Plan Review Notes
Plan Review Notes For Permit 08060582
Permit Number 08060582
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-23 14:58:54*****DENIED******
  
  
 1. THE SCOPE OF WORK SHALL NOT INTERFERE WITH EMERGENCY
 RESPONSE ACCESS TO THE BUILDING(S) OR THE VICINITY
 THEREOF (INCLUDING FIRE LANES) .
  
 2. PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
  
 3. STATIONARY GENERATORS USED FOR EMERGENCY OR STANDBY
 POWER SHALL BE INSTALLED , TESTED, AND MAINTAINED TO
 COMPLY WITH NFPA 110.
  
 4. DIESEL FUEL STORAGE SHALL COMPLY WITH NFPA 30.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722