 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE MANUFACTURERS SPECIFICATIONS REQUESTED IN THE
 PRIOR REVIEW, COMMENT #3, WERE NOT SUBMITTED, THE
 SCHEMATIC ON SHEET E2 DOES NOT CLEARLY INDICATE
 COMPLIANCE WITH 230.76 OR 225.31, 32. PLEASE SUBMIT
 SAME.
  
 2} SHEET E5 INDICATES A BONDING JUMPER IN THE EXISTING
 SWITCHGEAR IN VIOLATION OF 250.24(A)(5) "LOAD-SIDE
 GROUNDING CONNECTIONS A GROUNDING CONNECTION SHALL NOT
 BE MADE TO ANY GROUNDED CONDUCTOR ON THE LOAD SIDE OF
 THE SERVICE DISCONNECTING MEANS EXCEPT AS OTHERWISE
 PERMITTED IN THIS ARTICLE." THE NEUTRALS AND GROUNDS
 MUST BE SEPARATED IN THE EXISTING SWITCHBOARD AS THE
 APS IS NOW THE FIRST MEANS OF DISCONNECT. ALSO SEE
 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS
 AND 250.32(B)(1)----- "ANY INSTALLED GROUNDED CONDUCTOR
 SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING
 CONDUCTOR OR TO THE GROUNDING ELECTRODE(S).
  
 3} THE RESPONSE TO COMMENT #4 FROM THE PEVIOUS REVIEW
 WAS NOT CLEAR, SEE COMMENT #1.
  
 4} VERIFY THAT 250 MCM EQUIPMENT GROUND COMPLIES WITH
 250.122(F)(1). THIS WOULD DEPEND ON THE AMPERAGE RATING
 OF THE OCP. SEE COMMENT #1.
  
 5} THE NOTE "E" SHEET E5, SYSTEM GROUNDING LEGEND AND
 NOTE "9" SHEET E2 REGARDING ARTICLE 250.32(A)(2) AND
 USING THE NEUTRAL AS THE GROUND TO THE BUILDING IS NOT
 ALLOWED. ARTICLE 250.32(B)(2) STATES " GROUNDED
 CONDUCTOR WHERE (1) AN EQUIPMENT GROUNDING CONDUCTOR IS
 NOT RUN WITH THE SUPPLY TO THE BUILDING OR STRUCTURE,
 (2) THERE ARE NO CONTINUOUS METALLIC PATHS BONDED TO
 THE GROUNDING SYSTEM IN EACH BUILDING OR STRUCTURE
 INVOLVED". CONDITION #2 CANNOT BE MET . SEE E6"SYSTEM
 CONTROL WIRING, AND SHEET E4 INDICATING CONTROL WIRING
 RUNING BETWEEN THE STRUCTURE AND THE BUILDING AN
 EQUIPMENT GROUND PER 250.122 IS REQUIRED, MAKING
 COMMENT #2 A REQUIREMENT.
  