Plan Review Notes
Plan Review Notes For Permit 08060532
Permit Number 08060532
Review Stop P
Sequence Number 1
Notes
Date Text
2008-06-25 09:48:55****************PROVISO****************
 FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731