Plan Review Notes
Plan Review Notes For Permit 08060521
Permit Number 08060521
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-10 08:28:56DOUG ROBERTSON MET WITH THE CONTRACTOR TO PERFORM A
 PRE-INSPECT:
  
 1) THE ROOF WAS COMPLETED WITH NO PERMIT AND THE
 SHINGLES WERE NOT INSTALLED PER CODE. ALSO MISSING
 STARTER STRIPS.
  
 2) THE ROOF VALLEY SHINGLES WERE NOT INSTALLED PER THE
 MANUFACTURER SPECIFICATIONS.
  
 3) THE COMPLETED RECOVER DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF THE CODE AND AS PER THE FEBC:
  
 511.3RECOVERING VERSUS REPLACEMENT.
 NEW ROOF COVERINGS SHALL NOT BE INSTALLED WITHOUT FIRST
 REMOVING EXISTING ROOF COVERINGS WHERE ANY OF THE
 FOLLOWING CONDITIONS OCCUR:
 1. WHEN THE OLD ROOFING IS WATER-SOAKED OR DETERIORATED
 TO THE POINT THAT IT IS NOT SUITABLE AS A BASE FOR
 ADDITIONAL ROOFING.
 2. WHEN BLISTERS EXIST IN ANY ROOFING, UNLESS BLISTERS
 ARE CUT OR SCRAPED OPEN AND NAILED DOWN BEFORE APPLYING
 ADDITIONAL ROOFING.
 3. WHEN THE EXISTING ROOF SURFACE IS GRAVEL OR THE
 LIKE, THE GRAVEL SHALL BE THOROUGHLY REMOVED OR ALL
 LOOSE GRAVEL REMOVED AND APPROVED BASE MATERIAL
 INSTALLED BEFORE APPLYING ADDITIONAL ROOFING. 4. WHEN
 EXISTING ROOF IS SLATE OR THE LIKE. 5. WHEN SHEATHING
 OR SUPPORTS ARE DETERIORATED TO THE POINT THAT THE ROOF
 STRUCTURAL SYSTEM IS NOT SUBSTANTIAL ENOUGH TO SUPPORT
 RECOVERING.
 6. WHEN EXISTING ROOF HAS TWO OR MORE APPLICATIONS OF
 ANY TYPE ROOFING MATERIAL. CONFORMANCE WITH THIS ITEM
 SHALL MAKE REPLACEMENT MANDATORY.
 EXCEPTIONS:
 1. BUILDING AND STRUCTURES LOCATED WITHIN THE
 HIGH-VELOCITY HURRICANE ZONE SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1512 THROUGH 1525 OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2. WHEN THE STRUCTURAL DECK IS CONCRETE AND THE
 EXISTING ROOF IS FIRMLY ATTACHED TO THE DECK, THEN THE
 ROOF SHALL BE REMOVED DOWN TO A MINIMUM OF THREE PLIES
 OF MOISTURE-FREE FELTS.
 3. WHEN OTHERWISE APPROVED BY THE BUILDING OFFICIAL.
 4. WOOD SHINGLES OR SHAKES SHALL NOT BE PLACED OVER
 MORE THAN ONE APPLICATION OF WOOD OR ASPHALT SHINGLES.
 WOOD SHINGLES OR SHAKES MAY BE PLACED OVER EXISTING
 SHAKES WHEN INSTALLED IN ACCORDANCE WITH CEDAR SHAKE
 AND SHINGLE BUREAU RECOMMENDATIONS.