2008-07-22 14:02:15 | RESIDENTIAL (R3) ROOFING AND WINDOWS BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- ACCORDING TOCHIEF BUILDING INSPECTOR, KEN CONRAD, |
| COMMENTS ON PRE-INSPECTION VISITEXISTING ROOF |
| DOESN'T QUALIFY FOR ROOF RECOVERING. IN ADDITION |
| SHINGLES WHERE NOT PROPERLY INSTALLED. SEE ATTACHED |
| COPY OF KEN CONRAD'S COMMENTS DATED 6/24/08. |
| |
| ***NOTE: REVISE DESCRIPTION ON PERMIT APPLICATION TO |
| READ REMOVE EXISTING SHINGLES AND RE-ROOF WITH |
| SHINGLES. |
| |
| 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT |
| PICK UP. |
| |
| 3-NEED TO PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| REQUIRED BY DCA RULE 9B-72 FOR THE STORM SHUTTERS. |
| ALSO, PROVIDE A COMPLETE INSTALLATION SCHEDULE(SEE |
| ATTACHED SAMPLE)AS REQUIRED BY CITY'SIMPLEMENTATION |
| STANDARD FOR WIND-BORNE DEBRIS IMPACT PROTECTION. |
| ALSO, CLEARLY MARK ON STORM SHUTTERS DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE |
| USED ACCORDING TO THE DESIGN PRESSURES, EDGE DISTANCE, |
| CONNECTION TYPE, PANEL SPAN AND STRUCTURE TO BE |
| ATTACHED TO (CONCRETE, CONCRETE BLOCK OR WOOD)SEE |
| ANCHOR SPACING TABLES ONSHUTTERS DRAWINGS. |
| |
| 4- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS TO BE |
| REPLACED TO VERIFY COMPLIANCE WITH THE EGRESS |
| REQUIREMENTS FROM BEDROOMS.CLEARLY IDENTIFY ON KEY |
| PLAN SUBMITTED THE BEDROOM WINDOWS. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |