Plan Review Notes
Plan Review Notes For Permit 08060519
Permit Number 08060519
Review Stop B
Sequence Number 7
Notes
Date Text
2009-12-01 16:43:39BUILDING PLAN REVIEW
 PERMIT: 08060519
 ADD: 309 CLEMATIS ST
 CONT: WELLINGTON EQUESTRIAN
 TEL: (561)951-6729
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONS DATED:
 ARCHITECTURAL: REVISION# 4 NOV. 4/2009
 STRUCTURAL: REVISION# 3 NOV.2/ 2009
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) SHEET A-1 THE FRONT ENTRY STAIRWAY REVISION# 2 HAS
 NOT BEEN UPDATED, THE REVISION SUBMITTED DOES INDICATE
 THE STEEL COLUMN IN THE STAIRWELL BUT THE EGRESS
 CALCULATIONS FOR BOTH THE STAIRS AND FRONT ENTRY
 INDICATE THE PERMIT SET OF EGRESS CALCULATIONS, NOT
 WHAT IS CURRENTLY BUILT. PLEASE REVISE PLANS INDICATING
 THE REVISED SSTAIR AND DOORWAY EGRESS CALCULATION FOR
 THE FRONT STAIR AND ENTRY. PLEASE INCLUDE THE UPDATED 1
 HR RATED WALL ASSEMBLY WITH THE VERTICAL STEEL BEAMS
 LOCATED
 OUTSIDE OF THE 1 HOUR RATED ASSEMBLY. 1020.1.2
 PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN
 EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 PLEASE NOTE THE FIRST FLOOR ENTRY DOOR IS NOT LOCATED
 ON THE DOOR SCHEDULE LOCATED ON SHEET A-15.
  
 2) SHEET A-2 THE FRONT ROOFTOP STAIRWAY LOCATED IN THE
 BOTTOM RIGHT CORNER OF THE SHEET INDICATES A NEW 3'-0"
 DOOR THAT LEADS INTO THE MECHANICAL ROOM LOCATED
 BENEATH THE THIRD FLOOR LEVEL. PLEASE REVIEW SECTIONS :
 VERTICAL EXIT ENCLOSURES
 1020.1.1 OPENINGS AND PENETRATIONS. EXIT ENCLOSURE
 OPENING PROTECTIVE???S SHALL BE IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 715.
  
 EXCEPT AS PERMITTED IN SECTION 402.4.6, OPENINGS IN
 EXIT ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE.
  
 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 712. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 3A) SHEET A-3 INDICATES A NEW DUMBWAITER, NOT NOTED ON
 THIS SHEET BUT S-2, S-3 AND S-29 INDICATE AS SUCH.
 PLEASE PROVIDE THE WALL TYPES TO BE ASSOCIATED WITH THE
 SHAFT CONSTRUCTION A-3 DOES PROVIDE SHAFT AND WALL
 TYPES BUT NO WALL SECTION TAG IS PROVIDED FOR THE
 BUMBWAITER.. 3002.1 HOISTWAY ENCLOSURE PROTECTION.
 ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES
 SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 707.
 3002.1.1 OPENING PROTECTIVES. OPENINGS IN HOISTWAY
 ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7.
  
 3B) SHEET S-29 THE DUMBWAITER INDICATES HOW THE
 STRUCTURAL MEMBERS WILL BE INSTALLLED ON THE FIRST AND
 SECOND FLOOR BUT NO INFORMATION IS PROVIDED PAST THE
 SECOND FLOOR ROOF LINE. ADDITIONAL INFORMATION
 REQUIRED.
  
 3C) 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS AND
 DUMBWAITERS PENETRATING MORE THAN THREE STORIES SHALL
 BE PROVIDED WITH A MEANS FOR VENTING SMOKE AND HOT
 GASES TO THE OUTER AIR IN CASE OF FIRE.
  
 3D) PLEASE ALSO REVIEW SECTION 3006 FOR ELEVATOR
 MACHINE ROOMS SECTION 1-6.
  
 3E) A-3 THE ORIGINAL ISSUED PLANS DOES INDICATE A THIRD
 FLOOR KITCHEN THE NEW REVISION INDICATES THE REMOVAL OF
 THE KITCHEN AND ADDITIONAL DINING AREA, PLEASE UPDATE
 THE OCCUPANCY LOADS FOR THE THIRD FLOOR AND EGRESS OF
 THE STAIRS, IF THIS FLOOR CONTAINS THE HIGHEST
 CONCENTRATION OF OCCUPANTS. TABLE 1004.1.1& TABLE
 1005.1.
  
 4) SHEET A-5 WEST ELEVATION THE OPENING PROTECTIVES,
 FIRE SHUTTERS ARE STILL INDICATED ON PLANS, THERE HAS
 BEEN RECENT DISCUSSION WITH THE CONTRACTOR, DESIGNER
 AND OWNER ABOUT THE ELIMINATION OF THE FIRE SHUTTERS
 AND THE USE OF A HINGED COLLASPABLE WALL SECTION THAT
 WAS SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW UNDER
 ALTERNATE MATERIALS AND METHODS, TO DATE NO FORMAL
 SUBMITTAL HAS BEEN BROUGHT IN TO THE CITY FOR REVIEW.
 104.11 ALTERNATE MATERIALS, DESIGN OF METHODSOF
 CONSTRUCTION AND EQUIPMENT.
  
 5) SHEET A-8.1 INDICATES CABANAS TO BE DETERMINED BY
 OWNER, A SEPERATE PERMIT REVIEW AND ASSOCIATED FEES
 WILL BE REQUIRED. NOTE WIND INFORMATION OF HOW CABANAS
 WILL MEET WIND LOADING: WIND DESIGN SEECTION 1609.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  