2009-12-01 16:43:39 | BUILDING PLAN REVIEW |
| PERMIT: 08060519 |
| ADD: 309 CLEMATIS ST |
| CONT: WELLINGTON EQUESTRIAN |
| TEL: (561)951-6729 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISIONS DATED: |
| ARCHITECTURAL: REVISION# 4 NOV. 4/2009 |
| STRUCTURAL: REVISION# 3 NOV.2/ 2009 |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). |
| |
| 1) SHEET A-1 THE FRONT ENTRY STAIRWAY REVISION# 2 HAS |
| NOT BEEN UPDATED, THE REVISION SUBMITTED DOES INDICATE |
| THE STEEL COLUMN IN THE STAIRWELL BUT THE EGRESS |
| CALCULATIONS FOR BOTH THE STAIRS AND FRONT ENTRY |
| INDICATE THE PERMIT SET OF EGRESS CALCULATIONS, NOT |
| WHAT IS CURRENTLY BUILT. PLEASE REVISE PLANS INDICATING |
| THE REVISED SSTAIR AND DOORWAY EGRESS CALCULATION FOR |
| THE FRONT STAIR AND ENTRY. PLEASE INCLUDE THE UPDATED 1 |
| HR RATED WALL ASSEMBLY WITH THE VERTICAL STEEL BEAMS |
| LOCATED |
| OUTSIDE OF THE 1 HOUR RATED ASSEMBLY. 1020.1.2 |
| PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN |
| EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL |
| BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| PLEASE NOTE THE FIRST FLOOR ENTRY DOOR IS NOT LOCATED |
| ON THE DOOR SCHEDULE LOCATED ON SHEET A-15. |
| |
| 2) SHEET A-2 THE FRONT ROOFTOP STAIRWAY LOCATED IN THE |
| BOTTOM RIGHT CORNER OF THE SHEET INDICATES A NEW 3'-0" |
| DOOR THAT LEADS INTO THE MECHANICAL ROOM LOCATED |
| BENEATH THE THIRD FLOOR LEVEL. PLEASE REVIEW SECTIONS : |
| VERTICAL EXIT ENCLOSURES |
| 1020.1.1 OPENINGS AND PENETRATIONS. EXIT ENCLOSURE |
| OPENING PROTECTIVE???S SHALL BE IN ACCORDANCE WITH THE |
| REQUIREMENTS OF SECTION 715. |
| |
| EXCEPT AS PERMITTED IN SECTION 402.4.6, OPENINGS IN |
| EXIT ENCLOSURES OTHER THAN UNPROTECTED EXTERIOR |
| OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES |
| AND FOR EGRESS FROM THE ENCLOSURE. |
| |
| 1020.1.2 PENETRATIONS. PENETRATIONS INTO AND OPENINGS |
| THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR |
| REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY |
| FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 712. THERE SHALL BE NO PENETRATIONS OR |
| COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| 3A) SHEET A-3 INDICATES A NEW DUMBWAITER, NOT NOTED ON |
| THIS SHEET BUT S-2, S-3 AND S-29 INDICATE AS SUCH. |
| PLEASE PROVIDE THE WALL TYPES TO BE ASSOCIATED WITH THE |
| SHAFT CONSTRUCTION A-3 DOES PROVIDE SHAFT AND WALL |
| TYPES BUT NO WALL SECTION TAG IS PROVIDED FOR THE |
| BUMBWAITER.. 3002.1 HOISTWAY ENCLOSURE PROTECTION. |
| ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES |
| SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 707. |
| 3002.1.1 OPENING PROTECTIVES. OPENINGS IN HOISTWAY |
| ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7. |
| |
| 3B) SHEET S-29 THE DUMBWAITER INDICATES HOW THE |
| STRUCTURAL MEMBERS WILL BE INSTALLLED ON THE FIRST AND |
| SECOND FLOOR BUT NO INFORMATION IS PROVIDED PAST THE |
| SECOND FLOOR ROOF LINE. ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 3C) 3004.1 VENTS REQUIRED. HOISTWAYS OF ELEVATORS AND |
| DUMBWAITERS PENETRATING MORE THAN THREE STORIES SHALL |
| BE PROVIDED WITH A MEANS FOR VENTING SMOKE AND HOT |
| GASES TO THE OUTER AIR IN CASE OF FIRE. |
| |
| 3D) PLEASE ALSO REVIEW SECTION 3006 FOR ELEVATOR |
| MACHINE ROOMS SECTION 1-6. |
| |
| 3E) A-3 THE ORIGINAL ISSUED PLANS DOES INDICATE A THIRD |
| FLOOR KITCHEN THE NEW REVISION INDICATES THE REMOVAL OF |
| THE KITCHEN AND ADDITIONAL DINING AREA, PLEASE UPDATE |
| THE OCCUPANCY LOADS FOR THE THIRD FLOOR AND EGRESS OF |
| THE STAIRS, IF THIS FLOOR CONTAINS THE HIGHEST |
| CONCENTRATION OF OCCUPANTS. TABLE 1004.1.1& TABLE |
| 1005.1. |
| |
| 4) SHEET A-5 WEST ELEVATION THE OPENING PROTECTIVES, |
| FIRE SHUTTERS ARE STILL INDICATED ON PLANS, THERE HAS |
| BEEN RECENT DISCUSSION WITH THE CONTRACTOR, DESIGNER |
| AND OWNER ABOUT THE ELIMINATION OF THE FIRE SHUTTERS |
| AND THE USE OF A HINGED COLLASPABLE WALL SECTION THAT |
| WAS SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW UNDER |
| ALTERNATE MATERIALS AND METHODS, TO DATE NO FORMAL |
| SUBMITTAL HAS BEEN BROUGHT IN TO THE CITY FOR REVIEW. |
| 104.11 ALTERNATE MATERIALS, DESIGN OF METHODSOF |
| CONSTRUCTION AND EQUIPMENT. |
| |
| 5) SHEET A-8.1 INDICATES CABANAS TO BE DETERMINED BY |
| OWNER, A SEPERATE PERMIT REVIEW AND ASSOCIATED FEES |
| WILL BE REQUIRED. NOTE WIND INFORMATION OF HOW CABANAS |
| WILL MEET WIND LOADING: WIND DESIGN SEECTION 1609. |
| |
| JIM WITMER C. B. O. |