2009-11-20 07:41:20REVISIONS
  
 1. ROOF ACCESS DOOR TO INTERSTITIAL SPACE IS NOT
 ALLOWED WHICH IS SHOWN ON PAGE A-2.0. THIS OPENING IS
 TO BE SEALED WITH THE PROPER FIRE RATING OF THE EXIT
 ENCLOSURE FOR WHICH IT IS LOCATED.
  
 2. A NEW FIRE DEPARTMENT CONENCTION WAS TO HAVE BEEN
 INSTALLED ON THE SOUTH SIDE OF THE BUILDING TO REPLACE
 THE EXISTING SNOOT. THE NEW DOUBLE FIRE DEPARTMENT
 CONNECTION IS TO BE LOCATED WITHIN 150 FEET OF A FIRE
 HYDRANT. THE PLAN SEEM TO SUUEST THAT THE FIRE
 DEPARTMENT CONNECTION WILL BE PLACED ON THE RISER WHICH
 WOULD BE LOCATED ON THE NORTH SIDE OF THE BUILDING.
 PLEASE COORDINATE THE PLACEMENT OF THE NEW FIRE
 DEPARTMENT CONNECTION. KNOX-LOCKING CAPS ARE REQUIRED
 FOR THE NEW FIRE DEPARTMENT CONNECTION. THE EXISTING
 SNOOT NEEDS TO BE REMOVED.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW KITCHEN
 HOODS, DUCTS, AND FIRE SUPPRESSION SYSTEMS.
  
 4. ON PAGE E-12 IT APPEARS THAT FIRE ALARM EQUIPMENT
 WILL BE CONNECTED TO THE EXISTING FIRE ALARM CONTROL
 PANEL. ON PAGE E-11 HORN STROBES ARE SHOWN IN THE FIRE
 ALARM LEGEND. DUE TO THE OCCUPANT LOAD OF THE BUILDING
 SPEAKER STROBES WITH A VOICE EVACUATION MESSAGE WILL BE
 REQUIRED. A FIRE ALARM PERMIT IS REQUIRED FOR THE FIRE
 ALARM WORK PLANNED FOR THE THIRD FLOOR. THE ENTIRE
 BUILDING SHALL BE EQUIPPED WITH SPEAKER STROBE DEVICES.
  
 5. THE FIRE SPRINKLER DRAWINGS MAY NOT BE ILLUSTRATIVE
 TO THE WORK THAT HAS BEEN PERFORMED IN THE FIELD.
 PLEASE COORDINATE DRAWINGS WITH THE WORK AND CORRECT
 DISCREPANCIES.
  
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION