2009-11-20 07:41:20 | REVISIONS |
| |
| 1. ROOF ACCESS DOOR TO INTERSTITIAL SPACE IS NOT |
| ALLOWED WHICH IS SHOWN ON PAGE A-2.0. THIS OPENING IS |
| TO BE SEALED WITH THE PROPER FIRE RATING OF THE EXIT |
| ENCLOSURE FOR WHICH IT IS LOCATED. |
| |
| 2. A NEW FIRE DEPARTMENT CONENCTION WAS TO HAVE BEEN |
| INSTALLED ON THE SOUTH SIDE OF THE BUILDING TO REPLACE |
| THE EXISTING SNOOT. THE NEW DOUBLE FIRE DEPARTMENT |
| CONNECTION IS TO BE LOCATED WITHIN 150 FEET OF A FIRE |
| HYDRANT. THE PLAN SEEM TO SUUEST THAT THE FIRE |
| DEPARTMENT CONNECTION WILL BE PLACED ON THE RISER WHICH |
| WOULD BE LOCATED ON THE NORTH SIDE OF THE BUILDING. |
| PLEASE COORDINATE THE PLACEMENT OF THE NEW FIRE |
| DEPARTMENT CONNECTION. KNOX-LOCKING CAPS ARE REQUIRED |
| FOR THE NEW FIRE DEPARTMENT CONNECTION. THE EXISTING |
| SNOOT NEEDS TO BE REMOVED. |
| |
| 3. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW KITCHEN |
| HOODS, DUCTS, AND FIRE SUPPRESSION SYSTEMS. |
| |
| 4. ON PAGE E-12 IT APPEARS THAT FIRE ALARM EQUIPMENT |
| WILL BE CONNECTED TO THE EXISTING FIRE ALARM CONTROL |
| PANEL. ON PAGE E-11 HORN STROBES ARE SHOWN IN THE FIRE |
| ALARM LEGEND. DUE TO THE OCCUPANT LOAD OF THE BUILDING |
| SPEAKER STROBES WITH A VOICE EVACUATION MESSAGE WILL BE |
| REQUIRED. A FIRE ALARM PERMIT IS REQUIRED FOR THE FIRE |
| ALARM WORK PLANNED FOR THE THIRD FLOOR. THE ENTIRE |
| BUILDING SHALL BE EQUIPPED WITH SPEAKER STROBE DEVICES. |
| |
| 5. THE FIRE SPRINKLER DRAWINGS MAY NOT BE ILLUSTRATIVE |
| TO THE WORK THAT HAS BEEN PERFORMED IN THE FIELD. |
| PLEASE COORDINATE DRAWINGS WITH THE WORK AND CORRECT |
| DISCREPANCIES. |
| |
| |
| DENIED |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |