 ELECTRICAL APPROVED WITH EXCEPTION.
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. A REVISION
 IS REQUIRED CORRECTING THE LISTED DEFICIENCIES THIS
 PLAN PRIOR TO INSPECTION, OR A REINSPECTION FEE WILL
 RESULT.
  
 1} THE SOUTH STAIRWAY SHOWN ON SHEET E-2 DOES NOT MATCH
 SHEET A-2.0.CORRELATE SAME. IF THE DOORS SHOWN ON SHEET
 A-2.0ARE TO BE INSTALLED LOCATE THE EXIT SIGNS FOR
 SAME.
  
 2} THE FIXTURE COUNT AND TYPES ON THE SCHEDULE DO NOT
 CORRELATE WITH THE THE ONES ON THE FLOOR PLAN SHEETS
 E-2, 4, 5 AND 11. NEW FIXTURES HAVE BEEN ADDED BUT THE
 LIGHTING POWER DENSITIES REMAIN THE SAME AS THE PERMIT
 SET OF PLANS. RECALCULATE THE DENSITIES TO MATCH WITH
 THE PROPOSED FIXTURES.
  
 3} SHEETS E-9 & 10 PHOTOMETRICS DID NOT CHANGE TO
 REFLECT THE NEW FIXTURE WATTAGES, CORRECT SAME.
  
 4} TYPE "P-1" FIXTURES ARE NOT LISTED ON THE SCHEDULE.
  
 5} THE ROOM LABELED "STORAGE" AT THE SERVICE BAR,
 SHEETS E-3, 4, AND 5 , WAS LABELED "BEER" AND PRESUMED
 TO BE A COOLER ON THE PERMIT SET OF PLANS NO COMPRESSOR
 FOR THAT UNIT APPEARS IN THE PANEL SCHEDULES. PLEASE
 CLARIFY..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  