Plan Review Notes For Permit 08060519 |
Permit Number |
08060519 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2009-12-02 15:30:46 | | | | | ELECTRICAL APPROVED WITH EXCEPTION. | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. A REVISION | | IS REQUIRED CORRECTING THE LISTED DEFICIENCIES THIS | | PLAN PRIOR TO INSPECTION, OR A REINSPECTION FEE WILL | | RESULT. | | | | 1} THE SOUTH STAIRWAY SHOWN ON SHEET E-2 DOES NOT MATCH | | SHEET A-2.0.CORRELATE SAME. IF THE DOORS SHOWN ON SHEET | | A-2.0ARE TO BE INSTALLED LOCATE THE EXIT SIGNS FOR | | SAME. | | | | 2} THE FIXTURE COUNT AND TYPES ON THE SCHEDULE DO NOT | | CORRELATE WITH THE THE ONES ON THE FLOOR PLAN SHEETS | | E-2, 4, 5 AND 11. NEW FIXTURES HAVE BEEN ADDED BUT THE | | LIGHTING POWER DENSITIES REMAIN THE SAME AS THE PERMIT | | SET OF PLANS. RECALCULATE THE DENSITIES TO MATCH WITH | | THE PROPOSED FIXTURES. | | | | 3} SHEETS E-9 & 10 PHOTOMETRICS DID NOT CHANGE TO | | REFLECT THE NEW FIXTURE WATTAGES, CORRECT SAME. | | | | 4} TYPE "P-1" FIXTURES ARE NOT LISTED ON THE SCHEDULE. | | | | 5} THE ROOM LABELED "STORAGE" AT THE SERVICE BAR, | | SHEETS E-3, 4, AND 5 , WAS LABELED "BEER" AND PRESUMED | | TO BE A COOLER ON THE PERMIT SET OF PLANS NO COMPRESSOR | | FOR THAT UNIT APPEARS IN THE PANEL SCHEDULES. PLEASE | | CLARIFY.. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | |
|