Date |
Text |
2009-05-19 16:57:40 | BUILDING PLAN REVIEW- MAJOR WORKING DRAWING REVIEW |
| PERMIT: 08060519 |
| ADD: 309 CLEMATIS ST |
| CONT: PLAN REVIEW- CON JOHN WEBB |
| TEL: (561)312-6247 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 5-19-09 |
| 3RD REVIEW: |
| |
| 1) MISSING 2HR FIRE SHUTTER REQUIRED AS PER TABLE 602/ |
| TABLE 704.2 |
| |
| 2) BUILDING PROVISO: |
| 2A) LOUVER- WOOD LOUVER @ GAZEBO |
| 2B) STANDING SEAM METAL ROOF |
| |
| 3) PROVISO: SHEET A-3 VERSES S-6 THE GAZEBOS WEST WALL |
| ( KITHEN) DOES NOT SHOW UP ON THE STRUCTURAL PLANS WILL |
| NEED REVISION. |
| |
| 4) RED LINED A-11 DETAIL# 7 STAIR RISER INDICATED AS 7" |
| MINIMUM, TYPO 7" MAXIMUM RISER 1009.3. |
| |
| 5) SHEET A-12 DETAIL A/B WILL REQUIRE A 2 HR FIRE |
| RATING DETAIL, I SPOKE WITH KELLY YATES TODAY HE WILL |
| BE BRINGING OVER SHORTLY.PROVISO. |
| |
| 6) STRUCTURAL SHEETS DO NOT PROVIDE NAILING FOR THE T&G |
| 3/4" ROOF SHEATHING. COMPONENTS AND CLADDING, ROOF DECK |
| IS ABOVE 50', PROVISO. |
| |
| 7) SHEET S-22 DESIGNED TO ASCE 7-05 2007 FBC, THIS PLAN |
| WILL BE CONSIDERED TO BE DESIGNED UNDER THE 2004 FBC |
| WITH 2007 SUPPLEMENTS, NEEDS TO BE UPDATED. |
| |
| 8) SPOKE WITH ALLEN PRESSURE ZONE 2 CORRECT. |
| |
| 9) ONCE PERMIT APPLICATION IS MADE RADON FEES FOR 7,030 |
| SQ FT TO BE ADDED . |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 11) THRESHOLD BUILDING: |
| |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| THRESHOLD INSPECTOR: |
| WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. |
| CONTACT THE BUILDING OFFICIAL DOUG WISE FOR A MEETING |
| FOR THE SPECIAL INSPECTOR PROGRAM AT (561)805-6654 FOR |