Plan Review Notes
Plan Review Notes For Permit 08060519
Permit Number 08060519
Review Stop B
Sequence Number 4
Notes
Date Text
2009-05-19 16:57:40BUILDING PLAN REVIEW- MAJOR WORKING DRAWING REVIEW
 PERMIT: 08060519
 ADD: 309 CLEMATIS ST
 CONT: PLAN REVIEW- CON JOHN WEBB
 TEL: (561)312-6247
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 5-19-09
 3RD REVIEW:
  
 1) MISSING 2HR FIRE SHUTTER REQUIRED AS PER TABLE 602/
 TABLE 704.2
  
 2) BUILDING PROVISO:
 2A) LOUVER- WOOD LOUVER @ GAZEBO
 2B) STANDING SEAM METAL ROOF
  
 3) PROVISO: SHEET A-3 VERSES S-6 THE GAZEBOS WEST WALL
 ( KITHEN) DOES NOT SHOW UP ON THE STRUCTURAL PLANS WILL
 NEED REVISION.
  
 4) RED LINED A-11 DETAIL# 7 STAIR RISER INDICATED AS 7"
 MINIMUM, TYPO 7" MAXIMUM RISER 1009.3.
  
 5) SHEET A-12 DETAIL A/B WILL REQUIRE A 2 HR FIRE
 RATING DETAIL, I SPOKE WITH KELLY YATES TODAY HE WILL
 BE BRINGING OVER SHORTLY.PROVISO.
  
 6) STRUCTURAL SHEETS DO NOT PROVIDE NAILING FOR THE T&G
 3/4" ROOF SHEATHING. COMPONENTS AND CLADDING, ROOF DECK
 IS ABOVE 50', PROVISO.
  
 7) SHEET S-22 DESIGNED TO ASCE 7-05 2007 FBC, THIS PLAN
 WILL BE CONSIDERED TO BE DESIGNED UNDER THE 2004 FBC
 WITH 2007 SUPPLEMENTS, NEEDS TO BE UPDATED.
  
 8) SPOKE WITH ALLEN PRESSURE ZONE 2 CORRECT.
  
 9) ONCE PERMIT APPLICATION IS MADE RADON FEES FOR 7,030
 SQ FT TO BE ADDED .
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) THRESHOLD BUILDING:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT THE BUILDING OFFICIAL DOUG WISE FOR A MEETING
 FOR THE SPECIAL INSPECTOR PROGRAM AT (561)805-6654 FOR
 FURTHER INFORMATION
  
  