Notes
Date Text
2009-09-23 16:02:39DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 REVIEW DONE AT THE REQUEST OF THE BUILDING OFFICIAL FOR
 THE PREVIOUS REVIEWER:
  
 A. SHT P-1 SUBMITTED FOR REVISION DOES NOT INDICATE A
 REVISION NUMBER NOR DOES IT INDICATE WHERE THE REVISION
 IS LOCATED BECAUSE OF THE LACK OF REVISION CLOUDS. THAT
 SAID, THE SANITARY PIPING HAS BEEN DELETED, MANY
 FIXTURES HAVE BEEN DELETED FROM THE PLUMBING FIXTURE
 SCHEDULE SUCH AS THE W/C'S, LAVS, FAUCETS, URINAL,
 FLOOR SINKS, HOSE BIBB & WATER HEATER. PLEASE CLARIFY,
 HAVE THESE FIXTURES BEEN CHANGED, DELETED OR BOTH?
 SECTIONS 106.1.1, 106.2 & 106.1.3.
  
 B. SHT P-2 HAS COMPLETLY DIFFERENT INFORMATION THAN
 WHAT IS ON FILE FOR PUBLIC RECORD. WILL ALL THE
 INFORMATION FOR THE BARS BE DELETED? PLEASE CLARIFY.
 SECTIONS 106.1.1, 106.2 & 106.1.3.
  
 *****FROM PREVIOUS REVIEW PERMIT NUMBER 09020194****
  
 1. SHT P-2 SANITARY, (GREASE), RISER DIAGRAM. THE DISH
 WASHER SHALL DISCHARGE VIA A SEPARATE LINE, (SANITARY).
 ARTICLE III SECTION 90-124(7)(B).
  
 2. SHT P-2 SANITARY, (GREASE), RISER DIAGRAM. THE
 COMBINATION DRAIN & VENT SYSTEM SHALL BE PROVIDED WITH
 A DRY VENT CONNECTED AT ANY POINT WITHIN THE SYSTEM.
 SECTION 912.2.2. SYSTEM NOT VENTED.
  
 3. SHT P-2 POTABLE WATER RISER DIAGRAM. A WATER HAMMER
 ARRESTOR IS REQUIRED AT THE DISH WASHER. SECTION 604.9.
  
 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT
 OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH
 MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED
 DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR
 SERVICING & REPLACEMENT.
  
 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE
 TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE
 MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM.
 SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION
 402 PIPE SIZING.
  
 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES
 GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE
 INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E.
 FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1.
  
 7. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE
 GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE
 FORTHCOMING).
  
 8. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT
 OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD
 SHUT DOWN SHUT OFF VALVE.
  
 9. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL
 NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL
 APPLIANCES COMBINED. SECTION 410.2(1)(2)(3).
  
 10. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES
 GAS PIPE SIZE PER TABLE 402.4(2) WHICH IS .5 PSI OR
 LESS, BUT DELIVERY PRESSURE IS INDICATED AT 5 PSI.
 PLEASE CLAIRFY. SECTION 402.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  