2009-09-23 09:53:40 | |
| ** DENIED ** |
| |
| ** ** REVIEW DONE AT THE REQUEST OF THE BUILDING |
| OFFICIAL FOR PREVIOUS REVIEWER. |
| |
| 1) NOTE: PLANS SUBMITTED DO NOT MATCH. THE REVISED |
| SHEET E-2 SUBMITTED IS COMPLETELY DIFFERENT FORM |
| PREVIOUS SHEET E-2. IN FACT IT IS FOR A DIFFERENT FLOOR |
| ALTOGETHER. THE TITLE BLOCK INDICATES A REVISION DATE |
| OF 8/20/08 YET NO REVISIONS WERE MADE TO PLANS |
| COORDINATING WITH ANY NEW CHANGES FOR ELECTRICAL. |
| PLEASE KNOW THAT EVEN THE PREVIOUS E-3 SHEET HAS A |
| DIFFERENT FLOOR LAYOUT FOR POWER ETC. |
| THE R2 PANEL SCHEDULE INDICATES PANEL AS *EXISTING* YET |
| THE FILE SET OF PLANS INDICATES THIS PANEL AS NEW. |
| |
| 2) NOTE: PLEASE SUBMIT ACCURATE LOAD CALCULATIONS. LOAD |
| CALCULATIONS STATE PER NEC 220.87 FOR EXISTING LOADS. |
| HOWEVER HOW CAN THIS BE POSSIBLE WHEN THE NEW PANEL R2 |
| WAS ONLY JUST PERMITTED AND NOT YET INSTALLED? HOW |
| COULD THERE BE AN 24 MONTH DEMAND FROM FPL WHEN THE |
| PERMITTED LOAD/ADDITION OF FLOOR AND ALL OTHER |
| ELECTRICAL SYSTEMS ON PREVIOUS SUBMITTED PLANS HAVE NOT |
| YET BEEN INSTALLED TO DATE. |
| |
| *** IT IS TO BE CLEAR THAT THE FILE SET OF PLANS WERE |
| NOT REVIEW FOR CODE COMPLIANCE BY THIS REVIEWER. ONLY |
| THE SHEET E-2, E-3 AND PANEL SCHEDULES WERE LOOKED AT |
| FOR THERE RELEVANT CONTENTS BASED ON THE COORDINATION |
| OF REVISED DOCUMENTS SUBMITTED. |
| |
| ** IT SHOULD ALSO BE CLEAR THAT AS THERE IS INFORMATION |
| NOT YET SHOWN, REVISED OR MISSING ON PLANS THERE MAY BE |
| NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| POSSIBLE BE MADE AT THIS TIME. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |