Date |
Text |
2008-08-27 14:25:25 | BUILDING PLAN REVIEW |
| PERMIT: 08060519 |
| ADD: 309 CLEMATIS ST |
| CONT: PLAN REVIEW CON JOHN WEBB |
| TEL: (561)312-6247 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. 2 COPIES OF |
| RESPONCE COMMENTS WERE SUBMITTED AND COMMENTS 1 & 2 |
| WERE ONLY RESPONDED TOO. |
| |
| 1B) COMPLIED, 3 SETS OF DOCUMENTS SUBMITTED, THRESHOLD |
| BUILDING BECAUSE OF OCCUPANT LOAD. |
| |
| 1C) INFORMATIONAL |
| |
| 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E) 2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME |
| REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.NOTE THIS |
| IS AN ADDITION AND THE 2004 EXISTING BUILDING CODE |
| CHAPTER 9 WILL NEED TO BE ADDRESSED. SHEET DT-1 |
| INDICATES A LEVEL II ALTERATION, THIS MAY BE TRUE FOR |
| THE INTERIOR WORK UNDER ANOTHER PERMIT. THIS WORK IS TO |
| BE COVERED UNDER 2004 EXISTING BUILDING CODE CHAPTER 9 |
| ADDITIONS, PLEASE MAKE CORRECTIONS. |
| |
| 1F-H) COMPLIED. |
| |
| 2) 2ND REQUEST, THE DESIGNER OF RECORD HAS NOT PROVIDED |
| WHAT THE BASE DESIGN IS FOR WIND IN SHEETS A-1- A-4. |
| PLANS ARE MISSING THE WIND DESIGN CRITERIA. 1603.1.4 |
| WIND DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO |
| WIND LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND |
| LOADS GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING |
| SYSTEM OF THE BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. |
| WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 3) 2ND REQUEST, THIS BUILDING IS CLASSIFIED AS A |
| THRESHOLD BUILDING BECAUSE THE OCCUPANT LOAD IS GREATER |
| THAN 500 OCUPANTS. |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 3A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| 3B) THRESHOLD INSPECTOR: |
| WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 3C) COMPLIED. |
| |
| 4)SOILS REPORTS COMPLIED. |
| |
| 5) 2ND REQUEST, THE PLANS INDICATE TWO DIFFERENT |
| ENGINEERS IT APPEARS THAT ONE WILL BE A SPECIALTY |
| ENGINEER AND THE OTHER THE ENGINEER OF RECORD FOR THE |
| PROJECT, OR TO TAKE RESPONSIBILITY FOR THE PROJECT. THE |
| DESIGNER OF RECORD WILL NEED TO REVIEW ALL SHOP |
| DRAWINGS AND APPLY THEIR SHOP DRAWING STAMP ONCE PLANS |
| ARE REVIEWED AND APPROVED. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| |
| FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| |
| 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |