2009-06-05 15:07:43 | REVIEW FOR THIS SCOPE OF WORK PERFORMED UNDER PROJECT | | PERMIT #08070215 | | | | NOTE: EXTENSION AND RELOCATION OF EXISTING KITCHEN | | EXHAUST SHALL BE UNDER SEPARATE PERMIT AND EXCLUDED | | FROM THIS SCOPE OF WORK. | | | | NOTE FOR YOUR INFORMATION: MECHANICAL PLAN SHOWS THE | | KITCHEN EXHAUST FAN AT A MINIMUM HEIGHT OF 40" ABOVE | | THE ROOD SURFACE. ARCHITECTURAL PLANS SHOW THE FAN | | SURROUNDED ON 3 SIDES BY A 42" HIGH PARAPET. IF FAN IS | | TO BE LOCATED IN CLOSE PROXIMITY TO PARAPET (MIN. 2' | | SEPARATION) THE DISCHARGE OPENING OF THE FAN MUST BE | | HIGHER THAN THE PARAPET IN ACCORDANCE WITH FBC-M | | 506.5.5. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|