2009-09-23 16:10:45 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| REVIEW DONE AT THE REQUEST OF THE BUILDING OFFICIAL FOR |
| THE PREVIOUS REVIEWER: |
| |
| A. SHT P-1 SUBMITTED FOR REVISION DOES NOT INDICATE A |
| REVISION NUMBER NOR DOES IT INDICATE WHERE THE REVISION |
| IS LOCATED BECAUSE OF THE LACK OF REVISION CLOUDS. THAT |
| SAID, THE SANITARY PIPING HAS BEEN DELETED, MANY |
| FIXTURES HAVE BEEN DELETED FROM THE PLUMBING FIXTURE |
| SCHEDULE SUCH AS THE W/C'S, LAVS, FAUCETS, URINAL, |
| FLOOR SINKS, HOSE BIBB & WATER HEATER. PLEASE CLARIFY, |
| HAVE THESE FIXTURES BEEN CHANGED, DELETED OR BOTH? |
| SECTIONS 106.1.1, 106.2 & 106.1.3. |
| |
| B. SHT P-2 HAS COMPLETLY DIFFERENT INFORMATION THAN |
| WHAT IS ON FILE FOR PUBLIC RECORD. WILL ALL THE |
| INFORMATION FOR THE BARS BE DELETED? PLEASE CLARIFY. |
| SECTIONS 106.1.1, 106.2 & 106.1.3. |
| |
| *****FROM PREVIOUS REVIEW PERMIT NUMBER 09020194**** |
| |
| A. SEPARATE GAS PERMIT REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED: |
| |
| 1. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A LISTED SHUT |
| OFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH |
| MP REGULATOR. SECTION 409.4. A UNION IS REQUIRED |
| DOWNSTREAM OF THE SHUT OFF VALVE NEAR THE REGULATOR FOR |
| SERVICING & REPLACEMENT. |
| |
| 2. SHT P-2 GAS DISTRIBUTION ISOMETRIC. INDICATE THE |
| TOTAL BTU'S FOR THE EXISTING KITCHEN & DISTANCE TO THE |
| MOST REMOTE OUTLET IN THE KITCHEN ON THE RISER DIAGRAM. |
| SECTION 106.1.2 MORE INFORMATION REQUIRED AND SECTION |
| 402 PIPE SIZING. |
| |
| 4. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES |
| GAS PIPE SIZE PER TABLE 402.4(20) P.E. PIPE. PLEASE |
| INDICATE WHERE THE P.E. PIPE WILL BE INSTALLED. (P.E. |
| FOR OUTDOOR UNDERGROUND ONLY). SECTION 404.14.1. |
| |
| 5. SHT P-2 GAS DISTRIBUTION ISOMETRIC. PLEASE INDICATE |
| GAS TYPE. (IF LP GAS MORE COMMENTS WILL BE |
| FORTHCOMING). |
| |
| 6. SHT P-2 GAS DISTRIBUTION ISOMETRIC. A MANUAL SHUT |
| OFF VALVE IS REQUIRED UPSTREAM OF THE EMERGENCY HOOD |
| SHUT DOWN SHUT OFF VALVE. |
| |
| 7. SHT P-2 GAS DISTRIBUTION ISOMETRIC. SUBMIT MANUF. |
| SPECIFICATION SHEETS FOR THE UNIONS. INDICATE MODEL |
| NUMBER AND SHOW BTU CAPACITY FOR TOTAL LOAD OF ALL |
| APPLIANCES COMBINED. SECTION 410.2(1)(2)(3). |
| |
| 8. SHT P-2 GAS DISTRIBUTION ISOMETRIC. NOTE REFERENCES |
| GAS PIPE SIZE PER TABLE 402.4(2) WHICH IS .5 PSI OR |
| LESS, BUT DELIVERY PRESSURE IS INDICATED AT 5 PSI. |
| PLEASE CLAIRFY. SECTION 402. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |