Plan Review Notes For Permit 08060491 |
Permit Number |
08060491 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-07-30 09:34:35 | 2004 FBC W/2007 REVISIONS | | INSTALL SIGN ON HIGH RISE | | | | DENIED BY BUILDING | | | | 1) THE SIGN IS LOCATED ON A HIGH RISE BUILDING WITH A | | MEAN ROOF HEIGHT ABOVE 60 FEET. THE COMPONENT AND | | CLADDING WINDLOADS ARE REQUIRED TO BE CALCULATED USING | | ASCE7-02 OR WIND TUNNEL TESTING. SEE FBC 1609.1.1 THE | | SIMPLIFIED WINDLOAD METHOD CAN NOT BE USED FOR | | BUILDINGS WITH A MEAN ROOF HEIGHT OF 60 FEET AND THE | | BUILDING HAS A MEAN ROOF HEIGHT OF 237 FEET. REPEAT | | COMMENT. | | | | 2) THE FBC TABLE NUMBERS REFERENCED ON THE ENGINEERING | | WERE CHANGED IN THE REVISIONS TO THE 2004 FBC. PLEASE | | NOTE. | | | | 3)THE NEW DRAWINGS ARE REQUIRED TO HAVE THE CITY | | PLACE STAMP OF APPROVAL. | | | | 4) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | BE REQUIRED. FS 713 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|