2008-07-09 09:34:192004 FBC W/2007 REVISIONS
 INSTALL SIGN ON HIGH RISE
  
 DENIED BY BUILDING
  
 1) THE SIGN IS LOCATED ON A HIGH RISE BUILDING WITH A
 MEAN ROOF HEIGHT ABOVE 60 FEET. THE COMPONENT AND
 CLADDING WINDLOADS ARE REQUIRED TO BE CALCULATED USING
 ASCE7-02 OR WIND TUNNEL TESTING. SEE FBC 1609.1.1
  
 2) THE FBC TABLE NUMBERS REFERENCED ON THE ENGINEERING
 WERE CHANGED IN THE REVISIONS TO THE 2004 FBC. PLEASE
 NOTE.
  
 3) THE DESIGN CRITERIA IN THE TITLE BLOCK OF THE
 DRAWINGS INCORRECTLY SPECIFY THE 2004 FBG. PLEASE
 CHANGE TO FBC.
  
 4) PLEASE COORDINATE THE SIZE OF THE LETTERING ON THE
 FRONT AND SIDE VIEW DRAWINGS. FBC 106.1.1* CITY
 AMENDMENTS AND ZONING COMMENTS.
  
 5) THE VALUE FOR THE WORK IS TOO LOW. FBC 108.3* CITY
 AMENDMENTS STATES THAT FOR PERMITTING PURPOSES
 VALUATION OF WORK INCLUDES DESIGN, ENGINEERING, LABOR,
 MATERIALS, ELECTRICAL, OVERHEAD AND PROFIT. THE VALUE
 OF THE WORK BASED ON MARSHALL AND SWIFT HAS BEEN
 DETERMINED AS $13,540.00. PLEASE PAY ADDITIONAL FEES.
 NOTE:A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  