2008-10-02 09:47:51RESIDENTIAL (R2) SHUTTERS, BUILDING REVISION CHECKLIST.
 REVIEW UNDER 2004 FBC .
  
 1- BUILDING REVISION CALLS FOR SHUTTER PROTECTION ON
 WINDOWS. THIS TYPE OF BUILDING REQUIRES SHUTTERS
 INSTALLATION APPROVAL PLAN TO BE APPROVED BY THE
 BUILDING OFFICIAL. FOR PUBLIC SAFETY REASONS INDICATE
 HOW ARE REMOVABLE SHUTTERS GOING TO BE INSTALLED ON THE
 WINDOWS OF THIS MULTISTORY BUILDING BY THE APARTMENT
 OWNER IN THE EVENT OF A HURRICANE.
  
 2- DESIGN PRESSURES INDICATED IN THE CITY OF WEST PALM
 BEACH INSTALLATION SCHEDULE ARE ASSUMING THAT BUILDING
 IS DESIGNED AS ENCLOSED BUILDING. FURTHER RESEARCH
 NEEDS TO BE DONE. FOR SOME REASON OPENINGS HAVE NOT
 IMPACT GLAZING AND THERE ARE NOT EXISTING SHUTTERS.
 BUILDING CAN'T BE DESIGNED AS ENCLOSED IF THE OPENINGS
 ARE NOT PROTECTED. THEREFORE, NEED TO USE THE PARTIALLY
 ENCLOSED BUILDING DESIGN PRESSURES.
 ***NOTE: THIS ISSUE WILL BE BROUGHT TO THE BUILDING
 OFFICIAL ATTENTION FOR FURTHER DISCUSSION.
  
 2- FLORIDA PRODUCT APPROVAL FL8363-R1 SUBMITTED IS FOR
 2007 CODE VERSION. CURRENT CODE VERSION IS 2004. NEED
 TO PROVIDE PRODUCT APPROVAL FOR CURRENT CODE VERSION.
  
 3- INSTALLATION NOTES ON FLORIDA PRODUCT APPROVAL
 FL8363-R1 (2007 CODE VERSION) STATES THAT DEFLECTION
 NOT REQUIRED OUTSIDE HVHZ. AS MENTIONED ON PREVIOUS
 COMMENT THIS PRODUCT APPROVAL ONLY APPLIES TO 2007 CODE
 VERSION. THERE IS ANOTHER PRODUCT APPROVAL FOR 2004
 CODE VERSION WHICH DOESN'T HAVE THIS PROVISION.
 THEREFORE MUST FOLLOW DEFLECTION REQUIREMENTS.
  
 4- INSTALLATION SCHEDULE AND ANCHOR SCHEDULE
 HIGHLIGHTED ON PAGE 15 INDICATE THAT THE SUBSTRATE TO
 RECEIVE THE SHUTTERS IS 3000 PSI CONCRETE. SHUTTERS ARE
 GOING TO BE INSTALLED HORIZONTALLY. BUILDING HAS
 CONCRETE BLOCK WALLS, NOT CONCRETE. NEED TO REVISE
 INSTALLATION SCHEDULE ANCHOR SPACING USING THE CONCRETE
 BLOCK TABLES, EVEN IS THERE ARE CONCRETE BLOCK FILLED
 CELLS. OTHERWISE, PROVIDE COMPLETE TESTING SHOWING THAT
 FILLED CELLS ARE 3000PSI MIN.
  
 5- PERMIT VALUATION WAS UPDATED TO REFLECT THE
 ADDITIONAL SHUTTERS. THEREFORE OWES $25.72 FOR UPDATED
 VALUATION.
  
 6- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13 FLORIDA STATUTE.
  
 7- ENGINEER DESIGN PRESSURES CALCULATIONS HAVE A COPY
 OF HIS SIGNATURE INSTEAD OF HIS ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE AND SEC.
 61G15-23.002 OF ENGINEER'S FLORIDA ADMINISTRATIVE CODE
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712