Plan Review Notes
Plan Review Notes For Permit 08060414
Permit Number 08060414
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-17 08:21:28 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved