2008-06-20 16:36:06PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 SANITARY RISER DIAGRAM: THE ISOMETRIC
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. THE
 PROPOSED LAVATORY IS MISSING FROM THE RISER DIAGRAM.
 PER FBC - PLUMBING SECTION 701.1 SCOPE.
  
 2. SHEET A-1 SANITARY RISER DIAGRAM: CLEARLY INDICATE
 THAT A TWO-WAY CLEANOUT WILL BE INSTALLED AT THE
 JUCTION OF THE BUILDING DRAIN AND BUILDING SEWER. PER
 FBC - PLUMBING SECTION 708.3.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  