Plan Review Notes For Permit 08060339 |
Permit Number |
08060339 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-02 15:37:57 | 2004 FBC W/2007 REVISIONS | | REPLACE RETAINING WALL | | | | DENIED BY BUILDING | | | | 1) THE RETAINING WALL SHOWN ON THE SURVEY IS NOT | | LOCATED ON THE PROPERTY LISTED ON THE APPLICATION. ANY | | WORK IS REQUIRED TO BE WITHIN THE PROPERTY BOUNDARY | | LINES. | | | | 2) THE TOP OF THE MASONRY WALL IS REQUIRED TO HAVE A | | REINFORCED BOND BEAM. SEE FBC R609.2. | | | | 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | BE REQUIRED. | | | | 4) THE JOB NAME AND ADDRESS IS REQUIRED ON THE | | DRAWINGS. FBC 106.1.1* CITY AMENDMENTS. | | | | 5) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE DESIGN IS REQUIRED ON THE DRAWINGS.FBC 106.1.3* | | CITY AMENDMENTS. | | | | 6) SPECIFY THE APPLICABLE CODE ON THE DRAWINGS. 2004 | | FBC W/2007 REVISIONS.FBC 106.1.3* CITY AMENDMENTS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|