2008-07-17 12:23:39 | 2ND REVIEW: 7-17-08 |
| SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| |
| __OK 1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN |
| PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY |
| AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND |
| SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| ORIGINALS FAC61G15-23.002. |
| |
| __XX 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT. THE SPANS OF THE SHUTTERS INDICATED ON |
| THE INSTALLATION SCHEDULE DO NOT CORRESPOND WITH THE |
| OPENING HEIGHTS. IF ONE OF THE OPENINGS HAS A HEIGHT OF |
| 100 INCHES, HOW CAN THE SPAN BE 163 INCHES?SHOW THE |
| CORRECT SHUTTER SPANS ON THE INSTALLATION SCHEDULE. |
| |
| _OK 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| |
| _XX 4.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS |
| APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A |
| HIGHLIGHTER. ON SHEET #7 OF THE PRODUCT APPROVAL THE |
| DESIGN PRESSURE 47.2 CANNOT BE USED BECAUSE THE HOUSE |
| IS LOCATED IN AN EXPOSURE C PER YOUR INFORMATION. THE |
| NEXT DESIGN PRESSURE ON THE ANCHOR SCHEDULE IS 77PSF, |
| WHICH MEANS THIS ROW SHALL BE USED WHEN INDICATING THE |
| FASTENER SPACING INSTEAD OF 47.2 PSF. IF MORE THAN ONE |
| TYPE OF ANCHOR WILL BE USED, MAKE SURE THE CORRECT |
| DESIGN PRESSURE IS USED. SEE PAGES 7 AND 8. |
| |
| _OK 5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310. |
| |
| _OK 6.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS |
| WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH |
| THE INSTALLATION SCHEDULE, ITEM 4 ABOVE. |
| |