2008-07-11 10:58:51PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET S-1 AND S-2, ELECTRICAL BUILDING-FLOOR PLANS
 INDICATES 3 ALUMINUM SCUPPERS WITH DOWNSPOUTS AND SHEET
 S-6 INDICATES A SCUPPER AND CONDUCTOR HEAD- FRONT-SIDE
 DETAILS, HOWEVER THERE ARE NO SIZES OF THE SCUPPER,
 CONDUCTOR HEAD OR DOWNSPOUTS BEING INDICATED AS WELL AS
 THE REQUIRED SECONDARY ROOF DRAINAGE AND ROOF
 CALCULATION BEING INDICATED. PLEASE PROVIDE THE
 FOLLOWING INFORMATION PER THE FOLLOWING CODE
 REFERENCES.
  
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTION 1106.
  
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
  
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
  
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 NOTE: THE SCUPPER DETAIL ON SHEET S-6 INDICATES THE
 SCUPPER 3/4" ABOVE THE ROOF. IS IT THE INTENT TO HAVE
 3/4" OF WATER ON THE ROOF AS INDICATED?
  
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 2. THERE ARE NO FLOOR DRAINS OR POTABLE WATER HOSE
 BIBBS BEING INDICATED ON THE PLANS. IS IT THE INTENT
 NOT TO HAVE THESE ITEMS OR IS THIS AN OVERSIGHT?
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  