Plan Review Notes
Plan Review Notes For Permit 08060314
Permit Number 08060314
Review Stop M
Sequence Number 1
Notes
Date Text
2008-06-30 11:46:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS SHOW TWO AIR CONDITIONING SYSTEMS ARE TO BE
 INSTALLED, PLEASE SUBMIT A MECHANICAL (A/C) PLAN
 SHOWING THE EQUIPMENT LOCATION AND EQUIPMENT SCHEDULE,
 PER 2004 FBC 106.3.5.
  
 2) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S FOR THE
 2000 GALLON FUEL STORAGE TANK BEING INSTALLED, PER 2004
 FBC/M 1301.
  
 3) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S FOR THE
 DUTY FAN AND LOUVERS, PER 2004 FBC 1609.
  
 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 GENERATOR ROOM LOUVERS, SEE FS 553.842(1) AND FAC RULE
 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]