Plan Review Notes For Permit 08060314 |
Permit Number |
08060314 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-15 15:48:44 | ***DENIED*** | | | | 1) PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR | | PROPOSED 2000 GALLON DIESEL TANK. | | | | 2) DERM TO BE CONTACTED FOR APPROVAL OF THE 2000 GALLON | | DIESEL TANK. | | | | 3) PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR | | GENERATOR AND ASSOCIATED EQUIPMENT. | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED. | | | | | | 5) PLACARDING IN COMPLIANCE WITH NFPA 30 AND NFPA 704 | | TO BE PROVIDED ALONG WITH NO SMOKING SIGNS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|