2008-07-07 13:53:00** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE VERIFY WHY THE GENERATOR IS SHOWING GFI
 PROTECTION. IT IS UNCLEAR AT THIS TIME WHY THIS TYPE PF
 PERSONNEL PROTECTION IS BEING PROVIDED ON THE GENERATOR
 BREAKER.
 ** CODE SECTIONS SUCH AS 240.13, 230.95 REQUIRED GROUND
 FAULT BUT NOT IN THIS CASE.
  
 2)NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETSFOR THE NEW PROPOSED ATS AND GENERATOR.
 90.7, 110.3, 702.6
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 3) NOTE: PLEASE VERIFY THE NEW MAIN WHICH INDICATES A
 SHUNT TRIP BREAKER ACTUALLY STILL CONTAINS THE MANUAL
 MEANS OF DISCONNECT RATED FOR LOAD SERVED PER 230.76,
 230.79
  
 4) NOTE: PLEASE VERIFY THE NUMBER OF CONDUCTORS ON THE
 LINE SIDE OF THE TRANSFORMER.IT APPEARS TO INDICATE A
 NEUTRAL AND NOT AN EQUIPMENT GROUND.
 PLEASE VERIFY THE CONDUCTORS ON THE LOAD SIDE OF THE
 TRANSFORMER ALSO. WILL THE EQUIPMENT GROUNDING
 CONDUCTOR BE THE SAME SIZE?
 240.21, 310.16, 250.20 ETC
  
 5) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION OF THE
 TRANSFORMER. ALONG WITH THE CONDUCTOR SIZE. 250.20,
 250.50, 250.58, 25.66.
  
 6) NOTE: THE PHOTO-METRICS NOTED ON E-1 STATE
 REQUIREMENTS PER PALM BEACH COUNTY. THIS PROJECT IS
 LOCATED WITH THE CITY OF WEST PALM BEACH. THE LIGHTING
 AS SHOWN IS NOT REQUIRED.
 PLEASE BE SURE TO ADJUST LOCATION.
  
 7) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS FUEL
 TANKS/PLANS WILL BE REQUIRED TO BE STAMPED BY DERM.
 (DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT.
  
 8) NOTE: PLEASE SEE RISER AS THE EQUIPMENT GROUNDING
 CONDUCTORS FROM MAIN TO ATS AND ATS TO DISTRIBUTION
 BOARD ARE MISSING.
 250.110, 250.122 ETC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]