Plan Review Notes
Plan Review Notes For Permit 08060314
Permit Number 08060314
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-01 13:35:13BUILDING PLAN REVIEW
 PERMIT: 08060314
 ADD: 1025 23RD ST
 CONT: MURRAY LOGAN CONSTRUCRION
 TEL: (561)248-1473
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.SHEET
 S-1 INDICATES JUST AMENDMENTS PLEASE UPDATE PLANS TO
 INCLUDE THE CURRENT 2007 AMENDMENTS.
  
 2) PLEASE PROVIDE THE FOLLOWING INFORMATION TO ALLOW
 FOR A ACCCURATE PLAN REVIEW OF THIS PROJECT. 110.2* W.
 P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED
 FOR RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
  
 3) PROVIDE SOILS REPORT WITH THE MINIMUM SAFE BEAARING
 VALUE. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 6) PLANS FAIL TO INDICATE COMPLIANCE WITH 1816.1.
 TERMITE PROTECTION.
  
 7) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 7A) EXTERIOR DOORS
 7B) LOUVERS
 C) ROOF ASSEMBLIES
  
 8) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET S- 5 INDICATES 2000 GALLON DEISEL FUEL
 CONVAULT, PLEASE SUBMIT PRODUCT INFORMATION 414.5.5
 SPILL CONTROL, DRAINAGE AND CONTAINMENT.
  
 11) PLANS FAIL TO PROVIDE ANCHORAGE FOR THE GENERATOR ,
 ANCHORAGE AGAINST MOMENT OF OVERTURNING. 1609.1.3.
  
 12) SHEET A-7 THE LIGHT POLE DETAIL INDICATES THE
 DESIGN TO THE SOUTH FLORIDA BUILDING CODE PLEASE
 CORRECT TO THE 2007 FBC AND SUBMIT WIND CALCULATIONS.
  
 13) SHEET A-7 ANTENNA DETAIL PLEASE SUBMIT ENGINEERING
 FOR COMMUNICATIONS ANTENNA1609.1.1(7).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.