Plan Review Notes For Permit 08060276 |
Permit Number |
08060276 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-06-25 16:13:17 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FACFLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.SEE SHEET 5.CONNECTIN TYPE A REQUIRES 9" SPACING | | WITH A FACTOR OF .86 FOR A 3" EDGE DISTANCE.12" | | SPECIFIED ON THE INSTALLATION SCHEDULE, OPENINGS 6 AND | | 7.NOTE THAT YOU HAVE CIRCLED THIS ON THE PRODUCT | | APPROVAL (9" SPACING) BUT DID NOT USE THIS NUMBER ON | | THE INSTALLATION SCHEDULE.CHECK ALL. | | | | 2ND REVIEW, THE INSTALLATION SCHEDULE WAS REVISED TO | | 9".SEE FIRST LIST; A 3" EDGE DISTANCE REQUIRES A | | FACTOR OF .86, SEE PAGE 5.YOU HAVE CIRCLED THIS | | ALREADY ON THE PRODUCT APPROVAL, BUT DID NOT APPLY THE | | FACTOR TO THE ANCHOR SPACING.PLEASE REVISE THE | | INSTALLATION SCHEDULE AND CHECK ALL OTHER OPENINGS. |
|