Notes
Date Text
2008-06-25 16:13:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE SHEET 5.CONNECTIN TYPE A REQUIRES 9" SPACING
 WITH A FACTOR OF .86 FOR A 3" EDGE DISTANCE.12"
 SPECIFIED ON THE INSTALLATION SCHEDULE, OPENINGS 6 AND
 7.NOTE THAT YOU HAVE CIRCLED THIS ON THE PRODUCT
 APPROVAL (9" SPACING) BUT DID NOT USE THIS NUMBER ON
 THE INSTALLATION SCHEDULE.CHECK ALL.
  
 2ND REVIEW, THE INSTALLATION SCHEDULE WAS REVISED TO
 9".SEE FIRST LIST; A 3" EDGE DISTANCE REQUIRES A
 FACTOR OF .86, SEE PAGE 5.YOU HAVE CIRCLED THIS
 ALREADY ON THE PRODUCT APPROVAL, BUT DID NOT APPLY THE
 FACTOR TO THE ANCHOR SPACING.PLEASE REVISE THE
 INSTALLATION SCHEDULE AND CHECK ALL OTHER OPENINGS.