Plan Review Notes For Permit 08060247 |
Permit Number |
08060247 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-16 13:40:24 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLEASE FILL IN LINES 11 AND 12 ON THE ENERGY | | CALCULATIONS, PER 2004 FBC 13-607.1.C.1. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-103.3. | | | | 3) THE COOLING LOAD CALCULATIONS ARE SHOWING THE WRONG | | TOTAL AREA (1632), THIS SHOULD ONLY SHOW THE TOTAL | | SQUARE FEET UNDER AIR. SEE ATTACHED PROPERTY APPRAISER | | PRINT OUT SHOWING EXISTING SQ. FT. UNDER AIR THEN SEE | | THE PLANS AND SCALE THE NEW ADDITION, MY CALCULATION | | CAME UP WITH 1388 SQUARE FEET UNDER AIR. PLEASE CORRECT | | COOLING LOAD CALCULATIONS, PER 13-607.ABC.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|