Plan Review Notes
Plan Review Notes For Permit 08060247
Permit Number 08060247
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-01 11:40:462004 FBC W/2007 REVISIONS
 ADDITION TO SFD
  
 DENIED BY BUILDING
  
 1)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY (PH.233-5025). THE PLANS MUST BE
 STAMPED AND THE PAID RECEIPT SUBMITTED TO THE CITY
 BUILDING DEPARTMENT.
  
 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT. THE FORM LISTS R-5 WALL
 INSULATION AND THE PLANS SPECIFY R-4.5 (A MINIMUM OF
 R-5 IS REQUIRED BY METHOD A). PLEASE CORRECT. THE FORM
 LISTS R-30 CEILING INSULATION AND THE PLANS HAVE R-32.
 PLEASE CORRECT. SEE FBC 13-600.
  
 3) SHOW COMPLIANCE WITH 2004 FBC EXISTING BUILDING
 SECTION 904.2, WHICH REQUIRES SMOKE ALARMS IN THE
 EXISTING BUILDING AS WELL AS THE ADDITION. SEE ALSO
 R313.1.1.
  
 4) THE NEW BATHROOM IS REQUIRED TO HAVE A DOOR WITH A
 29" CLEAR OPENING, MEASURED FROM THE FACE OF THE DOOR
 TO THE OPPOSITE STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 R322.
  
 5) SPECIFY THE WALL THICKNESS OF THE 3" PIPE COLUMN.
 SPECIFY THE WELD TYPE AT THE BASE AND CAP OF THE
 COLUMN. PROVIDE A DETAIL OF THE COLUMN CAP, SHOWING THE
 NUMBER, SIZE, ETC. OF EMBEDS.
  
 6) PROVIDE WINDOW AND DOOR BUCK DETAILS. SEE FBC
 R613.6.1.1.
  
 7) SPECIFY HOW TERMITE PROTECTION WILL BE PROVIDED ON
 THE PLANS AS REQUIRED BY R320.1.
  
 8) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 9) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL
 EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 11) THE ROOF SHEATHING FASTENING SPECIFIED ON SHEET 1
 IS INCORRECT. SEE R803.2.3.1 SHEATHING FASTENINGS. WOOD
 STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO ROOF
 FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON CENTER
 AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY,
 0.42 < G < 0.49 IS USED, SPACING OF RING-SHANK
 FASTENERS SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3
 FOR 130 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE
 WITH FIGURE R803.2.3.1 .
  
 12) THE ROOF FASTENING SCHEDULE ON SHEET 3 DOES NOT
 SPECIFY RING SHANK NAILS. THE ROOF SHEATHING THICKNESS
 SPECIFIED ON SHEET 3 IS DIFFERENT THAN ON SHEET 1.
 PLEASE COORDINATE NOTES. SEE FBC R803.2.3.1 AND FBC
 106.1.1* CITY AMENDMENTS.
  
 13) ON SHEET 2 , A 140 MPH 3 SECOND GUST WIND SPEED
 WITH EXPOSURE B AND C IS SPECIFIED. ON SHEET 3 A 150
 MPH 3 SECOND GUST WIND SPEED AND EXPOSURE C IS
 SPECIFIED. PLEASE COORDINATE THE DESIGN DATUM. SEE R
 301.2.1.
  
 14) THE COMPONENT AND CLADDING PRESSURES FOR EXPOSURE C
 SPECIFIED ON SHEET 2 ARE TOO LOW. SEE TABLE R301.2(2)
 AND TABLE R301.2(3). THE ADJUSTMENT COEFFICIENT FOR
 EXPOSURE C WITH A 15' MRH IS 1.21. PLEASE REVISE OR
 SUBMIT SIGNED AND SEALED CALCULATIONS FOR THE COMPONENT
 AND CLADDING VALUES THAT ARE SPECIFIED ON THE PLANS.
  
 15)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 16) SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG
 WINDOWS, MULLIONS AND STORM PANELS THAT ARE TO BE
 REINSTALLED. SPECIFY THE MOUNT TYPE, FASTENERS,
 FASTENER SPACING, EDGE DISTANCE, GLASS SEPARATION, ETC.
 FOR THE STORM PANELS. CIRCLE ALL INFORMATION USED TO
 DETERMINE ADEQUATE INSTALLATION FROM THE STORM PANEL
 PRODUCT APPROVALS.
  
 17) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO
 INSTALL THE GAF MODIFIED ROOF SYSTEM. SUBMIT RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 OF THE ROOFING NOA.
  
 18) PLEASE SUBMIT ONE SET OF OLD PLANS WITH A RESPONSE
 LETTER INDICATING HOW AND WHERE ON THE PLANS THE
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]