2008-06-19 09:05:21 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} IT IS UNCLEAR IF THE ELECTRICAL SHOWN ON THE PLAN IS |
| NEW OR EXISTING AND THERE IS NO MENTION OF ELECTRICAL |
| WORK ON THE APPLICATION DESCRIPTION. CHANGE THE |
| APPLICATION TO INCLUDE THE SCOPE OF WORK. |
| |
| 2} 210.60 GUEST ROOMS OR GUEST SUITES |
| (A) GENERAL GUEST ROOMS OR GUEST SUITES IN HOTELS, |
| MOTELS, AND SIMILAR OCCUPANCIES SHALL HAVE RECEPTACLE |
| OUTLETS INSTALLED IN ACCORDANCE WITH 210.52(A) AND |
| 210.52(D). GUEST ROOMS OR GUEST SUITES PROVIDED WITH |
| PERMANENT PROVISIONS FOR COOKING SHALL HAVE RECEPTACLE |
| OUTLETS INSTALLED IN ACCORDANCE WITH ALL OF THE |
| APPLICABLE RULES IN 210.52. THIS ARTICLE APPLIES TO THE |
| WALLS THAT ARE AFFECTED UNDER LEVEL 2 ALTERATION. |
| |
| 3} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| ARTICLE AND PUT A ON THE PLAN FOR CLARITY IN THE |
| FIELD. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |