Plan Review Notes
Plan Review Notes For Permit 08060213
Permit Number 08060213
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-14 16:01:56*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.ON SHEET LS-1, IT APPEARS THAT THE NEW EXIT LIGHT
 IN THE CONVERTER CONTROL ROOM [124] DIRECTS PERSONS TO
 THE WAREHOUSE WHICH IS CONSIDERED A MORE HAZARDOUS
 AREA..PLEASE EXPLAIN.
  
 3.ON SHEET E-2, PLEASE EXPLAIN THE CARD READERS IN
 RELATION TO PERSON/PERSONS BEING ABLE TO EGRESS THROUGH
 EXIT DOOR(S) AS PER NFPA 101 - 7.2.1.6.2
  
 4.PLEASE PROVIDE LAYOUT OF THE FIRE SPRINKLER HEADS
 AND FIRE ALARM DEVICES FOR THIS REMODEL.IT IS
 UNDERSTOOD THAT SEPARATE PLANS AND PERMIT WILL BE
 PROVIDED ONCE THE MASTER PERMIT IS PRINTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  