Plan Review Notes For Permit 08060213 |
Permit Number |
08060213 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-14 16:01:56 | *****DENIED***** | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 2.ON SHEET LS-1, IT APPEARS THAT THE NEW EXIT LIGHT | | IN THE CONVERTER CONTROL ROOM [124] DIRECTS PERSONS TO | | THE WAREHOUSE WHICH IS CONSIDERED A MORE HAZARDOUS | | AREA..PLEASE EXPLAIN. | | | | 3.ON SHEET E-2, PLEASE EXPLAIN THE CARD READERS IN | | RELATION TO PERSON/PERSONS BEING ABLE TO EGRESS THROUGH | | EXIT DOOR(S) AS PER NFPA 101 - 7.2.1.6.2 | | | | 4.PLEASE PROVIDE LAYOUT OF THE FIRE SPRINKLER HEADS | | AND FIRE ALARM DEVICES FOR THIS REMODEL.IT IS | | UNDERSTOOD THAT SEPARATE PLANS AND PERMIT WILL BE | | PROVIDED ONCE THE MASTER PERMIT IS PRINTED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | | | | | |
|