2008-07-02 16:44:21 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} LOCATE PANEL "P2" ON THE ELECTRICALPLAN SO THAT |
| CLEARANCE REQUIREMENTS CAN BE REVIEWED PER 110.26. |
| |
| 2} PER 301.1 DECLARE THE OCCUPANCY TYPE FOR THE AREA |
| UNDER ALTERATION. |
| |
| 3} SHEET E1 ENERGY CALCULATIONSFOR LIGHTING DENSITIES |
| ARE ALL CALCULATED AT 1.1WATT/ SQ FT. APPARENTLY USING |
| THE USING THE BUILDING AREA METHOD TABLE 13-415.2.C.1. |
| INDICATE WHAT BUILDING TYPE WAS USED, SEE COMMENT #2. |
| |
| 4} SEE ARTICLE 645 NEC AND NFPA-75 REGARDING |
| REQUIREMENTS FOR THIS ROOM. LOCATE THE DISCONNECTING |
| MEANS PER 645.10 ON THE PLANS. |
| |
| NOTE: A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED PRIOR |
| TO INSTALLING THE ACCESS CONTROL SYSTEM |
| |
| PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| SHEETS TO EXPEDITE AND SUBMIT WRITTEN RESPONSE TO THE |
| COMMENTS MADE IN THIS REVIEW. |
| |
| PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE |
| SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN |
| ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN |
| AFFECTED AREAS FOR DEMOLITION AND MAKE SAVE SAME. ALL |
| TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH |
| ARTICLE 590 NEC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |